Schneider Electric ATH230U30N4
MPNATH230U30N4
Active
Variable speed drive, Altivar HVAC ATH200, ATH230, 3kW, 3hp, 380 to 500V, 3 phase, IP20, with EMC filter
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Connector type | RJ45 |
| Protection type | Line supply phase loss: drive Motor phase loss: motor Line supply overvoltage and undervoltage: drive Overheating protection: drive Overload: motor With PTC probes: motor Short-circuit between motor phases: drive Overcurrent between output phases and earth: drive |
| Range of product | Altivar HVAC ATH200 |
| Relay output type | Configurable relay logic R1A 1 NO electrical durability 100000 cycles Configurable relay logic R1B 1 NC electrical durability 100000 cycles Configurable relay logic R1C Configurable relay logic R2A 1 NO electrical durability 100000 cycles Configurable relay logic R2C |
| Analogue input type | AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits |
| Discrete input type | STO safe torque off, 24 V DC, impedance: 1.5 kOhm DI1...DI6 logic inputs, 24 V DC (30 V) DI5 programmable as pulse input: 0...30 kHz, 24 V DC (30 V) |
| Analogue output type | Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits |
| Discrete output type | Open collector DQ+ 0...1 kHz 30 V DC 100 mA Open collector DQ- 0...1 kHz 30 V DC 100 mA |
| Type of polarization | No impedance |
| Product or component type | Variable speed drive |
| Output voltage | <= power supply voltage |
| Supply voltage | 380...500 V - 15...10 % |
All specifications
| Parameter | Value |
|---|---|
| Relative symmetric mains voltage tolerance | 10 % |
| Line current | 11.1 A at 380 V 8.4 A at 500 V |
| Nominal output current | 7.1 A |
| Maximum switching current | Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1A, R1B, R1C on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1A, R1B, R1C, R2A, R2C on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 250 V AC Relay output R2A, R2C on resistive load, cos phi = 1: 5 A at 30 V DC |
| Maximum transient current | 7.9 A |
| Minimum switching current | Relay output R1A, R1B, R1C, R2A, R2C: 5 mA at 24 V DC |
| Apparent power | 7.3 kVA at 500 V |
| Motor power | 3.0 hp |
| Power dissipation in | 93 W |
| Output frequency | 0.599 kHz |
| Supply frequency | 50...60 Hz - 5...5 % |
| Switching frequency | 2...16 kHz adjustable 4...16 kHz with derating |
| Nominal switching frequency | 4 kHz |
| Relative symmetric network frequency tolerance | 5 % |
| Network number of phases | 3 phases |
| IP degree of protection | IP20 |
| Physical interface | 2-wire RS 485 |
| Communication port protocol | Modbus serial BACnet MS/TP |
| Mounting mode | Cabinet mount |
| EMC filter | Class C2 EMC filter integrated |
| Pollution degree | 2 |
| Relative humidity | 5...95 % without condensation or dripping water conforming to EN/IEC 60068-2-3 |
| Operating altitude | 1000...3000 m with current derating 1 % per 100 m |
| Maximum acceleration under shock impact (during operation) | 150 m/s² at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 10 m/s² at 13...200 Hz |
| Depth | 158 mm |
| Width | 140 mm |
| Height | 184 mm |
| Product weight | 2.1 kg |
| Standards | IEC 61800-5-1 IEC 61800-3 UL 508C IEC 61800-3 environment 1 category C2 IEC 61800-3 environments 2 category C3 IEC 60721-3 IEC 61508 IEC 13849-1 |
| Marking | CULus CE UKCA KC EAC ATEX RCM |
| Variant | Standard version |
| Data format | 8 bits, configurable odd, even or no parity 1or 2 stop |
| Noise level | 52 dB |
| Option card | Communication module for BACnet IP |
| Safety level | SIL 3 conforming to IEC 61508 PL = e conforming to ISO 13849-1 |
| Safety function | STO (safe torque off) |
| Method of access | Server Modbus serial Subordinate BACnet MS/TP |
| Device short name | ATH230 |
| Transmission rate | 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps 9.6, 19.2, 38.4, 76.8 kbit/s |
| Function available | Fire mode Run permissive PID controller Additional PID Damper control Underload detection for broken belt |
| Operating position | Vertical +/- 10 degree |
| Transmission frame | RTU MS/TP |
| Number of addresses | 0...247 0...127 |
| Product destination | Asynchronous motors Synchronous motors |
| Relay output number | 2 |
| Discrete input logic | Positive logic (source) Negative logic (sink) |
| Overvoltage category | III |
| Prospective line isc | 5 kA |
| Analogue input number | 3 |
| Braking to standstill | By DC injection |
| Discrete input number | 7 |
| Volume of cooling air | 37.3 m3/h |
| Analogue output number | 1 |
| Discrete output number | 1 |
| Motor slip compensation | Automatic whatever the load Adjustable 0...300 % Not available in voltage/frequency ratio (2 or 5 points) |
| Brake chopper integrated | True |
| Product specific application | HVAC |
| 4 quadrant operation possible | True |
| Electromagnetic compatibility | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Ambient air transport temperature | -25...70 °C |
| Synchronous motor control profile | Vector control without sensor |
| Asynchronous motor control profile | Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor - Energy Saving Voltage/frequency ratio, 2 points |
| Acceleration and deceleration ramps | Linear U S CUS Ramp switching Acceleration/deceleration ramp adaptation Acceleration/deceleration automatic stop with DC injection |
| Ambient air temperature for storage | -25...70 °C |
| Ambient air temperature for operation | -10...50 °C without derating 50...60 °C with derating factor |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 Class 3S2 according to IEC 60721-3-3 |
| With safety function safe torque off | True |
MPN
ATH230U30N4