Schneider Electric ATS430D17S6
MPNATS430D17S6
Active
Soft starter, Altivar Soft Starter ATS430, 17A, 208 to 600V AC, control supply 110 to 230V AC
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Connector type | 1 RJ45 Open style |
| Protection type | Phase failure mains Thermal protection mains Thermal protection starter Current overload motor Motor underload motor Excessive acceleration time motor Motor phase loss detection motor Protection against line phase inversion mains External thermal protection motor Short-circuit between motor phase and earth motor |
| Range of product | Altivar Soft Starter ATS430 |
| Discrete input type | STOP) digital input, 4.4 kOhm RUN) digital input, 4.4 kOhm DI3) digital input, 4.4 kOhm DI4) digital input, 4.4 kOhm |
| Type of polarization | No impedance Modbus serial |
| Product or component type | Soft starter |
| Ue power supply voltage | 208...600 V AC - 15...10 %) |
| Coil voltage | 24 V DC |
| [Us] control circuit voltage | 110...230 V AC 50-60 Hz - 15...10 % |
| Voltage | 600 V |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Overload current | 400 % Ie for 13 s |
All specifications
| Parameter | Value |
|---|---|
| [Ie] rated operational current | Normal duty 17 A in line 104 °F (40 °C)) |
| Power loss static current independent | 19 W |
| [In] rated current pwr loss specifctn | 17 A |
| Current limiting %In (5 x ie maximum) | 150...700 % |
| Power loss per device current dependent | 2 W |
| Apparent power | 70 VA |
| Motor power | 4 kW 230 V in line normal duty 7.5 kW 400 V in line normal duty 7.5 kW 440 V in line normal duty 9 kW 500 V in line normal duty 9 kW 525 V in line normal duty |
| Power supply frequency | 50...60 Hz - 20...20 % |
| Maximum horse power rating | 3 hp 208 V normal duty 5 hp 230 V normal duty 10 hp 460 V normal duty 15 hp 575 V normal duty |
| Power loss during starting | 133 W during starting at 40 °C at 400% In |
| Phases | 3 phase |
| Utilisation category | AC-3A AC-53A |
| IP degree of protection | IP20 |
| Physical interface | 2-wire RS 485 RJ45 2-wire RS 485 open style (DO, D1, PE, COM) |
| Communication port protocol | Modbus serial RJ45 Modbus serial open style (DO, D1, PE, COM) |
| Device connection | In line |
| Pollution degree | Level 3 |
| Relative humidity | 5...95 % without condensation or dripping water EN/IEC 60068-2-3 |
| Operating altitude | > 2000...4800 m with current derating 1 % per 100 m above 2000 m |
| Maximum acceleration under shock load (during storage) | 10 gn at 11 ms |
| Maximum acceleration under shock load (during transport) | 10 gn at 11 ms |
| Maximum acceleration under shock impact (during operation) | 15 gn at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 1 gn at 13...200 Hz |
| Depth | 6.7 in (169 mm) |
| Width | 5.1 in (130 mm) |
| Height | 10.7 in (273 mm) |
| Standards | EN/IEC 60947-4-2 UL 60947-4-2 IEC 60664-1 |
| Marking | CULus CE UKCA CCC RCM EAC KC |
| Category | US1CP1G22588 |
| Data format | 8 bits, odd, even or no parity, 1 or 2 bits to stop for Modbus serial RJ45 8 bits, configurable odd, even or no parity for Modbus serial open style (DO, D1, PE, COM) |
| On-load factor | 50 % |
| Internal bypass | True |
| Method of access | Slave Modbus serial |
| Device short name | ATS430 |
| Transmission rate | 4.8...38.4 kbps for Modbus serial RJ45 0.3...115.2 kbps for Modbus serial open style (DO, D1, PE, COM) |
| Function available | Single direction Pre-heating Power monitoring Condition monitoring User management Ports and services hardening Security event logging Cybersecure firmware update Small motor test |
| Operating position | Vertical +/- 10 degree |
| Transmission frame | RTU : 1 RJ45 RTU : open style (DO, D1, PE, COM) |
| Input compatibility | STOP digital input level 1 PLC EN/IEC 61131-2 RUN digital input level 1 PLC EN/IEC 61131-2 DI3 digital input level 1 PLC EN/IEC 61131-2 DI4 digital input level 1 PLC EN/IEC 61131-2 |
| Number of addresses | 0...247 Modbus serial |
| Product destination | Asynchronous motors |
| Discrete input logic | Digital input STOP 0...< 5 V Digital input RUN 0...< 5 V Digital input DI3 0...< 5 V Digital input DI4 0...< 5 V 470 Ohm |
| Service factor at ie | 100 |
| Discrete input number | 4 |
| Operating cycles (hour) | 10 cyc/h |
| Display screen available | True |
| Product specific application | Standard industrial machines |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-18 Electrostatic discharge level 3 conforming to IEC 61000-4-2 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5 Immunity to conducted disturbances radio-frequency level 3 conforming to IEC 61000-4-6 |
| Motor thermal protection class | Class 10E |
| Ambient air transport temperature | -40...158 °F (-40...70 °C) |
| Ambient air temperature for storage | -40...158 °F (-40...70 °C) |
| Integrated motor overload protection | True |
| Ambient air temperature for operation | -13...104 °F (-25...40 °C) (without derating) 104...140 °F (40...60 °C) (with current derating of 1 % per °C above 40 °C) |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3 |
| Maximum deflection under vibratory load (during storage) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibratory load (during storage) | 1 gn at 9...200 Hz 1.5 gn at 200...500 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Maximum deflection under vibratory load (during transport) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibratory load (during transport) | 1 gn at 9...200 Hz 1.5 gn at 200...500 Hz |
MPN