Schneider Electric ATS490D22Y
MPNATS490D22Y
Active
Soft starter, Altivar Soft Starter ATS490, 22A, 208 to 690V AC, control supply 110 to 230V AC
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Connector type | 1 RJ45 for connecting Modbus serial 1 RJ45 for connecting Modbus TCP/EtherNet/IP |
| Protection type | Phase failure mains Thermal protection starter Thermal protection motor Current overload motor Motor underload motor Excessive acceleration time motor Motor phase loss detection motor Protection against line phase inversion mains External thermal protection motor Protection delta inside wiring starter Short-circuit between motor phase and earth motor |
| Range of product | Altivar Soft Starter ATS490 |
| Discrete input type | DI1) digital input, 4.4 kOhm DI2) digital input, 4.4 kOhm DI3) digital input, 4.4 kOhm DI4) digital input, 4.4 kOhm STO) digital input, > 1 kOhm |
| Type of polarization | No impedance Modbus serial |
| Product or component type | Soft starter |
| Ue power supply voltage | 208...690 V AC - 15...10 %) |
| Coil voltage | 24 V DC |
| [Us] control circuit voltage | 110...230 V AC 50-60 Hz - 15...10 % |
| Voltage | 690 V |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Overload current profile | 400 % Ie for 13 s |
All specifications
| Parameter | Value |
|---|---|
| Rated current in heavy duty | 17 A at 104 °F (40 °C) heavy duty |
| [Ie] rated operational current | Normal duty 22 A in line 104 °F (40 °C)) |
| Power loss static current independent | 19 W |
| [In] rated current pwr loss specifctn | 22 A |
| Current limiting %In (5 x ie maximum) | 150...700 % |
| Power loss per device current dependent | 4 W |
| Apparent power | 70 VA |
| Motor power | 5.5 kW 230 V in the motor supply line normal duty 11 kW 400 V in the motor supply line normal duty 11 kW 440 V in the motor supply line normal duty 11 kW 500 V in the motor supply line normal duty 11 kW 525 V in the motor supply line normal duty 15 kW 660 V in the motor supply line normal duty 18.5 kW 690 V in the motor supply line normal duty 4 kW 230 V in the motor supply line heavy duty 7.5 kW 400 V in the motor supply line heavy duty 7.5 kW 440 V in the motor supply line heavy duty 9 kW 500 V in the motor supply line heavy duty 9 kW 525 V in the motor supply line heavy duty 11 kW 660 V in the motor supply line heavy duty 15 kW 690 V in the motor supply line heavy duty 9 kW 230 V to the motor delta terminals normal duty 18.5 kW 400 V to the motor delta terminals normal duty 7.5 kW 230 V to the motor delta terminals heavy duty 15 kW 400 V to the motor delta terminals heavy duty |
| Power supply frequency | 50...60 Hz - 20...20 % |
| Maximum horse power rating | 5 hp 208 V normal duty 7.5 hp 230 V normal duty 15 hp 460 V normal duty 20 hp 575 V normal duty 3 hp 208 V heavy duty 5 hp 230 V heavy duty 10 hp 460 V heavy duty 15 hp 575 V heavy duty |
| Power loss during starting | 281 W during starting at 40 °C at 400% Ie |
| Phases | 3 phase |
| Utilisation category | AC-3A AC-53A |
| IP degree of protection | IP20 |
| Physical interface | 2-wire RS 485 100-BASE-TX category 5 or industrial Ethernet |
| Communication port protocol | Modbus serial Modbus TCP/EtherNet/IP |
| Device connection | In the motor supply line Inside delta |
| Pollution degree | Level 3 |
| Relative humidity | 5...95 % without condensation or dripping water EN/IEC 60068-2-3 |
| Operating altitude | > 2000...4800 m with current derating 1 % per 100 m above 2000 m |
| Maximum acceleration under shock load (during storage) | 10 gn at 11 ms |
| Maximum acceleration under shock load (during transport) | 10 gn at 11 ms |
| Maximum acceleration under shock impact (during operation) | 15 gn at 11 ms |
| Maximum acceleration under vibrational stress (during operation) | 1 gn at 13...200 Hz |
| Depth | 7.3 in (185 mm) |
| Width | 6.3 in (160 mm) |
| Height | 11.1 in (283 mm) |
| Standards | EN/IEC 60947-4-2 UL 60947-4-2 IEC 60664-1 |
| Cybersecurity level and standard | Security level (SL) 1 IEC 62443-4-2 |
| Marking | CE CULus UKCA RCM CCC ATEX EAC KC |
| Category | US1CP1G22588 |
| Data format | 8 bits, configurable odd, even or no parity 1or 2 stop |
| Option card | Communication module CANopen daisy chain Communication module CANopen Sub-D Communication module CANopen open style Communication module Profibus DP V1 Communication module PROFINET |
| On-load factor | 50 % |
| Internal bypass | True |
| Method of access | Slave Modbus serial |
| Device short name | ATS490 |
| Transmission rate | 4.8...38.4 kbps 100 BASE TX |
| Function available | Pre-heating Smoke extraction Second motor set Deceleration with torque control Braking Boost Line contactor control Reverse contactor control Anti-jam Jog Borehole pump starting Condition monitoring Power monitoring Cybersecure firmware update |
| Operating position | Vertical +/- 10 degree |
| Transmission frame | RTU TCP/UDP |
| Input compatibility | DI1 discrete input level 1 PLC EN/IEC 61131-2 DI2 discrete input level 1 PLC EN/IEC 61131-2 DI3 discrete input level 1 PLC EN/IEC 61131-2 DI4 discrete input level 1 PLC EN/IEC 61131-2 STO discrete input level 1 PLC EN/IEC 61131-2 |
| Number of addresses | 0...247 Modbus serial |
| Product destination | Asynchronous motors |
| Discrete input logic | Digital input DI1 0...< 5 V Digital input DI2 0...< 5 V Digital input DI3 0...< 5 V Digital input DI4 0...< 5 V Digital input STO 0...< 5 V 470 Ohm |
| Service factor at ie | 100 |
| Discrete input number | 5 |
| Operating cycles (hour) | 10 cyc/h |
| Safe torque off | STO (safe torque off): SIL 1 conforming to IEC 61508 STO (safe torque off): PL c/category 2 conforming to ISO 13849 |
| Cybersecurity functions | True |
| Display screen available | True |
| Product specific application | Process and infrastructures |
| Electromagnetic compatibility | Conducted and radiated emissions level A conforming to IEC 60947-4-2 Damped oscillating waves level 3 conforming to IEC 61000-4-18 Electrostatic discharge level 3 conforming to IEC 61000-4-2 Immunity to electrical transients level 4 conforming to IEC 61000-4-4 Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3 Voltage/current impulse level 3 conforming to IEC 61000-4-5 Immunity to conducted interference caused by radio-electrical fields level 3 conforming to EN/IEC 61000-4-6 |
| Motor thermal protection class | Class 10E |
| Ambient air transport temperature | -40...158 °F (-40...70 °C) |
| Ambient air temperature for storage | -40...158 °F (-40...70 °C) |
| Integrated motor overload protection | True |
| Ambient air temperature for operation | -13...104 °F (-25...40 °C) (without derating) 104...140 °F (40...60 °C) (with current derating of 1 % per °C above 40 °C) |
| Environmental class (during operation) | Class 3C3 according to IEC 60721-3-3 Class 3S3 according to IEC 60721-3-3 |
| With safety function safe torque off | True |
| Maximum deflection under vibratory load (during storage) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibratory load (during storage) | 1 gn at 9...200 Hz 1.5 gn at 200...500 Hz |
| Maximum deflection under vibratory load (during operation) | 1.5 mm at 2...13 Hz |
| Maximum deflection under vibratory load (during transport) | 1.75 mm at 2...9 Hz |
| Maximum acceleration under vibratory load (during transport) | 1 gn at 9...200 Hz 1.5 gn at 200...500 Hz |
MPN