Schneider Electric C100N32AFM — Miniature Circuit Breakers (MCB)

Schneider Electric C100N32AFM ComPacT NS, 1000 A, 50 kA at 4

MPNC100N32AFM
Active

Schneider Electric ComPacT NS new generation, fixed-mount 3P, 1000 A at 50 °C, MicroLogic 2.0 A electronic trip, 50 kA Icu at 415 V AC, IP40, IK07.

$3,872.09Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C100N32AFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C100N32AFM — Ratings
ParameterValue
Rated current (In)1000 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C100N32AFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 690 V In 4000 cycles at 690 V In/2 5000 cycles at 440 V In 6000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C100N32AFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C100N32AFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C100N32AFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C100N32AFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C100N32AFM is a ComPacT NS new generation fixed-mount circuit breaker, rated 1000 A at 50 °C with a MicroLogic 2.0 A electronic trip unit. It provides L (long-time overload) and I (instantaneous short-circuit) protection per EN/IEC 60947-2, which means it's certified for distribution-level fault interruption and selective coordination in industrial panels. Breaking capacity is 85 kA Icu at 220/240 V AC, 50 kA Icu at 380/415 V AC, and 30 kA Icu at 660/690 V AC. The N breaking capacity code indicates 50 kA at 415 V AC.

Fixed mounting on a backplate, 3-pole configuration with a 70 mm connection pitch. Front connections top and bottom make it straightforward to bus or cable into a panel — no rear-access complications. Dimensions are 327 mm high, 210 mm wide, 147 mm deep, so plan for a 210 mm wide slot in the enclosure cutout.

Frequently asked questions

What is the breaking capacity of C100N32AFM at 415 V?

50 kA Icu at 380/415 V AC, 50/60 Hz, conforming to IEC 60947-2.

MPN
C100N32AFM