The Schneider Electric C100N32AFM is a ComPacT NS new generation fixed-mount circuit breaker, rated 1000 A at 50 °C with a MicroLogic 2.0 A electronic trip unit. It provides L (long-time overload) and I (instantaneous short-circuit) protection per EN/IEC 60947-2, which means it's certified for distribution-level fault interruption and selective coordination in industrial panels. Breaking capacity is 85 kA Icu at 220/240 V AC, 50 kA Icu at 380/415 V AC, and 30 kA Icu at 660/690 V AC. The N breaking capacity code indicates 50 kA at 415 V AC.
Fixed mounting on a backplate, 3-pole configuration with a 70 mm connection pitch. Front connections top and bottom make it straightforward to bus or cable into a panel — no rear-access complications. Dimensions are 327 mm high, 210 mm wide, 147 mm deep, so plan for a 210 mm wide slot in the enclosure cutout.