Skip to main content
Schneider Electric C106TM016

Schneider C106TM016 ComPacT NSX trip unit, TM-D, 16 A, 4 poles (discontinued)

MPNC106TM016
Active

Schneider Electric ComPacT NSX, new generation C106TM016 trip unit, TM-D thermal-magnetic, 16 A at 40 °C, 4 poles, 3D (no neutral protection), fixed mount, Class II, EN/IEC 60947-2.

$43.56Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C106TM016 key specifications
ParameterValue
Network typeAC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Range of productComPacT NSX100...250
Product or component typeTrip unit
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable
[Ue] rated operational voltage690 V AC 50/60 Hz
Network frequency50/60 Hz
Poles description4P
Protected poles description3D
IP degree of protectionIP40 conforming to IEC 60529

All specifications

C106TM016 additional specifications
ParameterValue
Circuit breaker mounting modeFixed
Pollution degree3 conforming to IEC 60947-1
Electrical shock protection classClass II
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameTM-D
Neutral positionLeft
Trip unit rating16 A at 40 °C
Device applicationDistribution
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Neutral protection settingsNo protection (3D)
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Tr] Long-Time protection delay adjustment range120...400 s at 1.5 x In 15 s at 6 x Ir
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range190 A

Product details

Overview

The C106TM016 is a TM-D thermal-magnetic trip unit for the Schneider ComPacT NSX100 molded-case circuit breaker, rated 16 A at 40 °C with 4 poles and 3D protection (no neutral pole).

The C10F3TM025 is a 3-pole TM-D trip unit rated 25 A at 40 °C with an 85 kA breaking capacity at 440 V AC, versus the C106TM016's 4-pole 16 A rating. Pick the C10F3TM025 when the BOM requires 3 poles and a higher continuous current.

MPN
C106TM016