Connection is front-facing via compression lugs or busbars; the connection pitch is 35 mm with spreaders, 27 mm without. The IP40 enclosure and IK07 impact resistance suit panel-mount indoor use where occasional tool contact is expected.
Electrical durability and environmental limits
Rated for 20 000 mechanical cycles and 20 000 electrical cycles at 440 V In/2, 10 000 at 440 V In, 10 000 at 690 V In/2, and 5 000 at 690 V In. Power dissipation is 4.6 W per pole. Pollution degree 3 (IEC 60664-1) and overvoltage category III. No earth-leakage protection built in — specify an external RCD if needed.