Three-pole construction (3P) suits three-phase distribution, and the Category A utilisation rating (per EN/IEC 60947-2) confirms it is designed for distribution duty, not motor-starting coordination.
Mounts on a backplate in horizontal or vertical orientation. The 9-module pitch (81 mm wide, 137 mm tall, 80 mm deep) is a standard MCCB footprint — plan the gland plate and DIN-rail fill accordingly. IP40 enclosure protection keeps dust out of a panel interior; no washdown rating, so keep it inside the cabinet. Connection terminals accept compression lugs or busbars, with front-facing connections on both line and load sides.
Certified to EN/IEC 60947-2, with suitability for isolation marked. Pollution degree 3 (IEC 60664-1) means it tolerates conductive pollution in industrial panels. Overvoltage category III suits fixed-installation distribution. Mechanical durability is 20,000 cycles; electrical durability is 20,000 cycles at 440 V at rated current, halving to 10,000 cycles at 2× rated current — the duty cycle matters if the breaker sees frequent switching.