Skip to main content
Schneider Electric C1BN2TM10HD

Schneider Electric C1BN2TM10HD

MPNC1BN2TM10HD
Active

Circuit breaker, ComPacT NSX1200N DC, 50kA/600VDC, 2 poles, TM-DC trip unit 1000A, without bare cable connector

$3,423.37 – $4,480.37Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C1BN2TM10HD key specifications
ParameterValue
Control typeToggle
Network typeDC
Protection typeL : for overload protection (thermal) I : for short-circuit protection (magnetic)
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Instantaneous protection pick-up adjustment type iiAdjustable
Long-time pick-up adjustment type ir (thermal protection)Adjustable
Voltage750 V DC conforming to IEC 60947-2
[Ue] rated operational voltage600 V DC
[Uimp] rated impulse withstand voltage8 kV conforming to IEC 60947-2
Breaking capacity50 kA Icu at 24...300 V DC 1 pole conforming to IEC 60947-2 50 kA Icu at 300...600 V DC 2 poles in series conforming to IEC 60947-2
Current1000 A at 40 °C

All specifications

C1BN2TM10HD additional specifications
ParameterValue
Breaking capacity codeN 50 kA 600 V DC
[Ics] rated service breaking capacity12.5 kA at 24...300 V DC conforming to IEC 60947-2 12.5 kA at 300...600 V DC conforming to IEC 60947-2
Poles description2P
Protected poles description2D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch45 mm
Upside connectionFront
Downside connectionFront
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
Electrical shock protection classClass II on front face
Depth110 mm
Width185 mm
Height485 mm
Product weight9.4 kg
Electrical durability2000 cycles at 600 V In/2 1000 cycles at 600 V In
Mechanical durability5000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
Trip unit nameTM-DC
Number of slots6 slot(s)
Trip unit rating1000 A at 40 °C
Device short nameNSX1200 DC
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Trip unit protection functionsLI
Ambient air temperature for storage-50...85 °C
Ambient air temperature for operation-25...70 °C
[Ir] long-time protection pick-up adjustment range0.7...1 x In
[Ii] instantaneous protection pick-up adjustment range2.5...5 x In
MPN
C1BN2TM10HD