Schneider Electric C320H4FM
MPNC320H4FM
Active
Circuit breaker frame, ComPacT NS3200H, 70kA at 415VAC, 3200A, 4P, fixed, manually operated, without control unit
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026
Specifications
| Parameter | Value |
|---|---|
| Product range | ComPacT |
| Product range (series) | ComPacT NS1600b...3200 new generation |
| Product/component type | Basic frame |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 3200 A at 50 °C |
| Breaking capacity | 125 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated service breaking capacity (Ics) | 94 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 64 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 64 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz |
| Rated insulation voltage (Ui) | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated impulse withstand voltage (Uimp) | 8 kV conforming to IEC 60947-2 |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Utilisation category | Category B |
| Overvoltage category | III |
| Parameter | Value |
|---|---|
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
| Electrical durability (cycles) | 1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 3000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2 |
| Mechanical durability (cycles) | 5000 cycles conforming to IEC 60947-2 |
| Parameter | Value |
|---|---|
| Mounting support | Backplate |
| Mounting mode | Fixed |
| Control type | Manually operated |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -25...70 °C |
| Storage ambient temperature | -50...85 °C |
| IP degree of protection | IP40 conforming to IEC 60529 |
| Pollution degree | 3 conforming to IEC 60947 |
| Parameter | Value |
|---|---|
| Standards | IEC 60947-2 |
MPN
C320H4FM