Schneider Electric G12E3A125 — Miniature Circuit Breakers (MCB)

Schneider Electric G12E3A125 GoPact MCCB 125, 3P, 125 A, 15

MPNG12E3A125
Active

Schneider Electric GoPact MCCB 125, 3P, 125 A, 15 kA at 415 V AC, thermal-magnetic TM-D trip, grey RAL 7035, fixed mount.

$99.45Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12E3A125 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12E3A125 — Ratings
ParameterValue
Rated current (In)125 A at 40 °C
Poles configuration3P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12E3A125 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)5000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12E3A125 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12E3A125 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12E3A125 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12E3A125 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12E3A125 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.8...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric G12E3A125 is a GoPact MCCB 125 — a 3-pole fixed-mount moulded-case circuit breaker with a thermal-magnetic TM-D trip unit rated 125 A at 40 °C. The LI protection (thermal for overload, magnetic for short-circuit) is the standard curve for distribution feeders, not motor-starting duty — the utilisation category A confirms it is not intended for frequent switching under load. Rated operational voltage is 415 V AC 50/60 Hz, insulation voltage 440 V AC — both per EN/IEC 60947-2.

Mounting and integration into a panel

Mounts fixed to a backplate — no DIN-rail clip. The 75 mm width, 130 mm height, and 60 mm depth fit standard MCCB cutouts in distribution boards. Screw terminals on both front-facing line and load sides; connection pitch is 25 mm. The grey RAL 7035 housing matches typical modular enclosure colour schemes.

MPN