Skip to main content
Schneider Electric G80N3E800 — Miniature Circuit Breakers (MCB)

Schneider Electric G80N3E800

MPNG80N3E800
Active

Circuit breaker, GoPact MCCB 800, 3 poles, 50kA at 415VAC, 800A, ETU trip unit, adjustable thermal protection, up to 50°C

$1,052.47Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jun 2026

Specifications

G80N3E800 — Identification
ParameterValue
Product nameGoPact MCCB 800
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G80N3E800 — Ratings
ParameterValue
Rated current (In)800 A at 40 °C 800 A at 50 °C
Poles configuration3P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G80N3E800 — Protection
ParameterValue
Trip unit technologyElectronic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)3000 cycles at 415 V In
Mechanical durability (cycles)15000 cycles
G80N3E800 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G80N3E800 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G80N3E800 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G80N3E800 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity50 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity50 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G80N3E800 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.25...1 x In
Trip unit protection functionsLSI
MPN
G80N3E800