Skip to main content
Schneider Electric GS1NG3 — Contactors

GS1NG3 TeSys GS fuse switch disconnector body, 250 A, 3P, DI

MPNGS1NG3
Active

Schneider Electric TeSys GS fuse switch disconnector body, GS1NG3, 3 poles, DIN rail mount, 250 A rated operational current, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

GS1NG3 — Identification
ParameterValue
Product / component typeFuse switch disconnector body
GS1NG3 — Contacts & Poles
ParameterValue
Pole configuration3P
GS1NG3 — Environmental
ParameterValue
IP degree of protectionIP20 IEC 60529 with terminal cover)
Protective treatment / pollution degreeTH
Fire resistance1562 °F (850 °C) fuse cover IEC 60695-2-1 1760 °F (960 °C) body IEC 60695-2-1
GS1NG3 — Approvals
ParameterValue
StandardsIEC 60947-3 IEC 60269-2 IEC 60269-1

Product details

The GS1NG3 is a TeSys GS fuse switch disconnector body — the main chassis that accepts the fuse carrier and operating handle for a 3-pole DIN-rail-mounted disconnecting point. Rated at 250 A operational current in AC-23A and AC-23B duty at 400 V, it handles motor switching and distribution disconnects where the load includes moderate overloads during start-up. Breaking capacity is 2000 A at 400 V AC-23B, and making capacity is 2500 A at the same voltage — meaning it can close onto a fault and interrupt it within those limits without welding or arcing damage.

Designed to IEC 60947-3 (switch-disconnector standard) and the fuse-assembly standards IEC 60269-1 and IEC 60269-2, so it coordinates with gG/gI fuse links for branch-circuit protection. Fire resistance tested to IEC 60695-2-1: the fuse cover withstands 1562 °F (850 °C) and the body 1760 °F (960 °C), which is a glow-wire test that confirms the thermoplastic won't propagate a fire under fault conditions.

Integration notes

Power circuit connections accept bars or screw terminals for 95 to 240 mm² flexible copper — sized for the 250 A continuous thermal current (Ith) at 40 °C ambient. Tightening torque for power terminals is 25 N·m — a standard torque wrench setting for this conductor range.

Frequently asked questions

What are the key ratings for the GS1NG3?

Rated operational current is 250 A in AC-23A/B at 400 V. Breaking capacity is 2000 A at 400 V AC-23B. Rated insulation voltage is 750 V AC. Impulse withstand voltage is 8 kV.

What standards does the GS1NG3 comply with?

It complies with IEC 60947-3 (switch-disconnector), IEC 60269-1, and IEC 60269-2 (fuse assembly standards).

How is the GS1NG3 mounted and what is its IP rating?

It mounts on a DIN rail or plate. With the terminal cover fitted, the IP rating is IP20 per IEC 60529.

MPN
GS1NG3