Schneider Electric GV3L326 — Miniature Circuit Breakers (MCB)

TeSys GV3L326 Motor Circuit Breaker, 32 A, 100 kA Breaking C

MPNGV3L326
Obsolete

Schneider Electric TeSys Deca GV3L326, motor circuit breaker, 3-pole, 32 A In, magnetic trip, 100 kA breaking capacity at 400 V AC, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GV3L326 — Identification
ParameterValue
Product nameTeSys GV3
Product rangeTeSys Deca
Product/component typeMotor circuit breaker
Device applicationMotor protection
GV3L326 — Ratings
ParameterValue
Rated current (In)32 A
Poles configuration3P
Breaking capacity100 kA Icu at 230/240 V AC 50/60 Hz 100 kA Icu at 400/415 V AC 50/60 Hz 50 kA Icu at 440 V AC 50/60 Hz 12 kA Icu at 500 V AC 50/60 Hz 6 kA Icu at 690 V AC 50/60 Hz
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz conforming to IEC 60947-2
Utilisation categoryCategory A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1
GV3L326 — Protection
ParameterValue
Trip unit technologyMagnetic
Suitability for isolationYes conforming to IEC 60947-1
Electrical durability (cycles)50000 cycles for AC-3 at 415 V In
Mechanical durability (cycles)50000 cycles
GV3L326 — Mechanical
ParameterValue
Control typeRotary handle
Terminal tightening torque6 N.m - on lugs-ring terminals
Width55 mm
Height132 mm
Depth136 mm
GV3L326 — Environmental
ParameterValue
Operating ambient temperature-20...60 °C
Storage ambient temperature-40...80 °C
IP degree of protectionIP20 conforming to IEC 60529
GV3L326 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 EN/IEC 60947-4-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 IEC/EN 60335-1:Clause 30.2 IEC/EN 60335-2-40:Annex JJ
GV3L326 — Electrical
ParameterValue
[Ics] rated service short-circuit breaking capacity100 % at 230/240 V AC 50/60 Hz 100 % at 400/415 V AC 50/60 Hz 100 % at 440 V AC 50/60 Hz 50 % at 500 V AC 50/60 Hz 50 % at 690 V AC 50/60 Hz

Product details

The GV3L326 is a 3-pole motor circuit breaker from the TeSys Deca range, rated 32 A continuous and built for motor protection in AC-3 duty. That 32 A In is the uninterrupted current it carries — match it to the full-load current of your motor, not the nameplate horsepower alone. The magnetic trip fires at 448 A, so it handles inrush without nuisance tripping on DOL starts up to about 15 kW at 400 V. That's a high-fault rating for a 32 A frame — it lets you place this breaker close to a large transformer or a high-capacity bus without needing upstream current-limiting fuses.

The 55 mm width and 132 mm height fit a standard motor-starter footprint — leaves room alongside a contactor on the same rail. Connection pitch is 17.5 mm without spreaders, so power wiring lands on a predictable grid. Tighten lugs to 6 N·m. IP20 finger-safe terminals are standard for enclosed panels. No washdown rating — keep this behind a gland plate or enclosure door.

What it isolates and where it runs

The rotary handle gives a visible break position. Ambient range is -20 to 60 °C operating, -40 to 80 °C storage, with no derating needed up to 3000 m altitude. Climatic withstand per IACS covers marine and humid environments.

Frequently asked questions

What compliance documentation does Schneider provide for the GV3L326?

The breaker carries UL 60947-4-1, CSA C22.2 No 60947-4-1, and multiple IEC/EN standards. RoHS and REACH declarations are standard for the TeSys Deca range.

What is the breaking capacity at 400 V?

100 kA Icu at 400/415 V AC. That is the maximum fault current the breaker can safely interrupt at that voltage level.

What motor power does this breaker cover at 400 V?

15 kW at 400/415 V AC, 50/60 Hz. At 500 V it covers 18.5 kW, and at 690 V it covers 22 kW.