Skip to main content
Schneider Electric LP4K090083BW3 — Contactors

Schneider LP4K090083BW3 TeSys K Contactor 4P 20A 24VDC Obsol

MPNLP4K090083BW3
Obsolete

Schneider Electric TeSys K contactor, LP4K090083BW3, 4P (2 NO + 2 NC), AC-1 ≤440V 20A, 24 V DC coil, obsolete.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LP4K090083BW3 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationResistive load
LP4K090083BW3 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz
Utilisation categoryAC-1
LP4K090083BW3 — Contacts & Poles
ParameterValue
Pole configuration4P
LP4K090083BW3 — Environmental
ParameterValue
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LP4K090083BW3 — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
LP4K090083BW3 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LP4K090083BW3 is a TeSys K 4-pole contactor with a 2 NO + 2 NC pole configuration, rated 20 A in AC-1 utilisation category at 690 V AC 50/60 Hz for resistive loads. Rated breaking capacity reaches 110 A at 415 V and 440 V, and 80 A at 500 V per IEC 60947 — meaning it can interrupt fault currents well above its continuous rating, which matters for coordination with upstream protection.

The power circuit average impedance is 3 mOhm at 20 A 50 Hz, so voltage drop across the contacts stays negligible even at full load. Operates in ambient temperatures from -25 to 50 °C and stores from -50 to 80 °C, with no derating required up to 2000 m altitude. Overvoltage category III and rated impulse withstand voltage of 8 kV mean it's suitable for fixed-installation panels connected to the mains supply.

This part is obsolete per the manufacturer.

Certified to EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Rated insulation voltage is 600 V per UL 508 and CSA C22.2 No 14, and 690 V per IEC 60947-4-1. Flame retardance meets V1 per UL 94 and Requirement 2 per NF F 16-101/102.

Frequently asked questions

What are the key ratings of LP4K090083BW3?

4 poles (2 NO + 2 NC), AC-1 rated operational current 20 A at 690 V AC, 24 V DC coil with built-in diode suppression, rated breaking capacity 110 A at 415 V, mechanical durability 30 million cycles, and operating rate 3600 cycles per hour.

MPN
LP4K090083BW3