Skip to main content
Schneider Electric LR97D015E — Contactors

Schneider Electric LR97D015E Electronic Overcurrent Relay, 0

MPNLR97D015E
Obsolete

Schneider Electric LR97 series, electronic overcurrent relay, LR97D015E, thermal protection adjustment 0.3...1.5 A, rated supply voltage 48 V AC/DC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LR97D015E — Identification
ParameterValue
Product / component typeElectronic overcurrent relay
LR97D015E — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Operating altitude2000 m
Protective treatment / pollution degreeTH conforming to IEC 60068
Fire resistance850 °C conforming to IEC 60695-2-1
LR97D015E — Approvals
ParameterValue
StandardsIEC 60947 IEC 60255-6
LR97D015E — Mechanical
ParameterValue
Width45 mm
Height67.5 mm
Depth67.5 mm

Product details

The Schneider Electric LR97D015E is an electronic overcurrent relay from the LR97 series, designed for motor protection in control panels. It detects locked rotor, mechanical jamming (I > 3 x Isetting), phase failure, and overload conditions where Imax exceeds the set threshold. The thermal protection adjustment range spans 0.3...1.5 A, with a tripping threshold of 0.3...1.3 A, making it suited for protecting small to medium motor loads on a 48 V AC/DC control supply.

Rated supply voltage is 48 V AC/DC — this is the coil voltage, not the motor power circuit. The relay operates on either AC or DC control power at 50/60 Hz, which simplifies panel wiring when both supply types are present. The reset options include automatic reset with a fixed 120 s delay, electrical reset by interrupting the supply for minimum 0.1 s, and manual reset. The 120 s automatic delay prevents immediate restart after a fault, which is standard for compressor or conveyor applications where rapid cycling could damage the load. Mounts directly on a contactor or on a DIN rail, occupying 45 mm width on the rail.

Designed to IEC 60947 and IEC 60255-6 standards, with a rated insulation voltage of 600 V (CSA/UL) and 690 V per IEC 60947-4-1. Surge withstand is 6 kV per IEC 61000-4-5, and dielectric strength is tested at 2 kV 50 Hz per IEC 60255-5.

Frequently asked questions

What is the thermal protection adjustment range?

The thermal protection adjustment range is 0.3...1.5 A, with a tripping threshold of 0.3...1.3 A. This covers small motor protection applications on a 48 V AC/DC control supply.

What reset options does the LR97D015E offer?

Three reset modes are available: automatic reset with a fixed 120 s delay, electrical reset by interrupting the supply for at least 0.1 s, and manual reset. The 120 s automatic delay prevents rapid restart after a fault.

What standards does the LR97D015E comply with?

The relay complies with IEC 60947 and IEC 60255-6. Rated insulation voltage is 600 V (CSA/UL) and 690 V per IEC 60947-4-1. Surge withstand is 6 kV per IEC 61000-4-5.

MPN
LR97D015E