LTMTIN42BD key specifications
ParameterValue
Input typeDigital input x4
Output signal2 xdigital output
Protection typeEarth fault protection external Temperature protection Analog input protection DI interlock protection
Product or component typeExtension module
Contacts type and compositionWithout
Short-circuit withstand100 kA conforming to EN/IEC 60947-4-1
Voltage690 V EN/IEC 60947-1
[Uimp] rated impulse withstand voltage0.8 kV current or voltage measurement circuit EN/IEC 60947-4-1 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Load current10 A 250 V AC/DC 5 A 30 V DC
Current state 0 guaranteedDigital input 0...12 V 5 mA 10 ms
Current state 1 guaranteedDigital input 18...30 V 5 mA 10 ms
Permissible power480 VA AC-15), Ie = 2 A, 500000 cycles output) 30 W DC-13), Ie = 1.25 A, 500000 cycles output)

All specifications

LTMTIN42BD additional specifications
ParameterValue
Maximum output switching frequency2 Hz
IP degree of protectionIP20
Mounting modeFlush-mounted
Connection pitch0.2 in (5.0 mm)
Connections - terminalsControl circuit connector 1 0.0003...0.004 in² (0.2...2.5 mm²) AWG 24...AWG 14)flexible stranded without cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.5 mm²) AWG 24...AWG 16)flexible stranded without cable end Control circuit connector 1 0.0003...0.004 in² (0.2...2.5 mm²) AWG 24...AWG 14)solid without cable end Control circuit connector 2 0.0003...0.002 in² (0.2...1.0 mm²) AWG 24...AWG 18)solid without cable end Control circuit connector 1 0.0004...0.004 in² (0.25...2.5 mm²) AWG 24...AWG 14)flexible stranded with cable end with insulation Control circuit connector 2 0.0008...0.002 in² (0.5...1.5 mm²) AWG 20...AWG 16)flexible stranded with cable end with insulation Control circuit connector 1 0.0004...0.004 in² (0.25...2.5 mm²) AWG 24...AWG 14)flexible stranded with cable end without insulation Control circuit connector 2 0.0003...0.002 in² (0.2...1.0 mm²) AWG 24...AWG 18)flexible stranded with cable end without insulation
Pollution degree3
Operating altitude<= 6561.68 ft (2000 m) without derating
Depth4.8 in (120.7 mm)
Width1.8 in (45 mm)
Height2.4 in (61 mm)
StandardsEN/IEC 60947-4-1 UL/CSA 60947-4-1
RangeTeSys
SupplyVia the controller
CategoryUS10I1222335
Fire resistance1202 °F (650 °C) EN/IEC 60695-2-12 1760 °F (960 °C) UL 94
Device short nameLTMT
Tightening torqueControl circuit 4.4 lbf.in (0.5 N.m) flat 0.1 in (3 mm)
Device applicationEquipment monitoring and control
Measurement accuracy1 % current 0.3...3 A) 1 % current 2.5...25 A) 3 % current 7...70 A) 3 % current 10...100 A) 1 % voltage 110...690 V) +/- 2.5 % earth fault current external measurement +/- 2.5 % earth fault current external measurement current > 0.03 A in the 0.3...3 A range) +/- 3...5 % earth fault current internal measurement current > 0.03 A in the 0.3...3 A range) +/- 30 min/year internal clock current > 0.25 A in the 2.5...25 A range) +/- 3...5 % earth fault current internal measurement current > 0.25 A in the 2.5...25 A range) +/- 3...5 % earth fault current internal measurement current > 0.7 A in the 7...70 A range) +/- 3...5 % earth fault current internal measurement current > 1 A in the 10...100 A range) +/- 2 % Temperature +/- 2 % THD measurement +/- 2...5 % active and reactive energy +/- 3...6 % power factor
Overvoltage categoryIII
Protective treatment12 x 24 hour cycles EN/IEC 60068-2-30
Mechanical robustnessShocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27 Vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 Vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6
Maximum operating rate1800 cyc/h
Electromagnetic compatibilityElectrostatic discharge, level 3, 8 kV air, 4 kV contact Fast transient bursts, level 3, 2 kV Immunity to electromagnetic interference, level 3, 10 V/m Immunity to shock waves, level 3, 2 kV
Ambient air temperature for storage-40...176 °F (-40...80 °C)
Ambient air temperature for operation-4...158 °F (-20...70 °C)
MPN