Schneider Electric LUCMT1BL
MPNLUCMT1BL
Obsolete
LUCMT1BL - MULTIFUNCTION CONTROL UNIT by TELEMECANIQUE
$233.68Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Load type | 3-phase motor - cooling: self-cooled - setting factory setting 3-phase motor - cooling: self-cooled, force cooled - setting settable Single-phase motor - cooling: self-cooled, force cooled - setting settable |
| Range of product | TeSys Ultra |
| Product or component type | Multifunction control unit |
| Immunity to voltage dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
| Coil voltage | 24 V DC |
| Voltage | 250 V conforming to IEC 60947-6-2 250 V conforming to UL 60947-4-1 250 V conforming to CSA C22.2 No 60947-4-1 |
| Control circuit voltage limits | 20...28 V for DC circuit 24 V in operation 14.5 V for DC circuit 24 V drop-out |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60947-6-2 |
| Typical current consumption | 130 mA at 24 V DC I maximum while closing 60 mA at 24 V DC I rms sealed |
| Rated motor current adjustment range | 0.35...1.05 A |
| Network frequency | 40...60 Hz |
| Phase failure sensitivity | Yes |
All specifications
| Parameter | Value |
|---|---|
| Utilisation category | AC-41 AC-44 AC-43 |
| IP degree of protection | IP20 front panel and wired terminals conforming to IEC 60947-1 IP20 other faces conforming to IEC 60947-1 IP40 front panel outside connection zone conforming to IEC 60947-1 |
| Physical interface | RS485 multidrop - connector(s): RJ45 - location: front panel - communication protocol: Modbus RTU 19200 bit/s |
| Shock resistance | 10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27 |
| Operating altitude | 2000 m |
| Vibration resistance | 2 gn, 5...300 Hz, power poles open conforming to IEC 60068-2-6 4 gn, 5...300 Hz, power poles closed conforming to IEC 60068-2-6 |
| Depth | 60 mm |
| Width | 45 mm |
| Height | 66 mm |
| Standards | EN 60947-6-2 IEC 60947-6-2 UL 508 CSA C22.2 No 14 |
| Range | TeSys |
| Reset | Automatic reset - setting: setting range Manual - setting: factory setting Manual - setting: setting range Remote reset - setting: setting range |
| Fixing mode | Plug-in (front face) |
| Return time | <= 200 ms |
| User language | English - setting factory setting English, French, German, Italian, Spanish - setting settable |
| Operating time | 35 ms opening for control circuit 70 ms closing for control circuit |
| Fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12 650 °C conforming to IEC 60695-2-12 |
| Heat dissipation | 2 W for control circuit |
| Device short name | LUCM |
| Time before reset | 1...1000 s - reset manual or automatic reset - setting settable 120 s - reset manual - setting factory setting |
| Compatibility code | LUCM |
| Device application | Motor control Motor protection |
| Tripping threshold | 14.2 x Ir +/- 20 % |
| Protective treatment | TH conforming to IEC 60068 |
| Information displayed | Average current (factory setting) Average current (settable) Cause of last 5 faults (settable) Current in phase (settable) Earth leakage current (settable) Phase imbalance (settable) Thermal state of motor (settable) |
| Thermal overload class | Class 5...30 - frequency limit: 50...60 Hz - temperature compensation: -25...55 °C conforming to IEC 60947-6-2 Class 5...30 - frequency limit: 50...60 Hz - temperature compensation: -25...55 °C conforming to UL 508 |
| Immunity to microbreaks | 3 ms |
| Main function available | Overload, no-load running Protection against phase failure and phase imbalance Protection against overload and short-circuit Manual or automatic reset Earth fault protection Log function Differentiation of thermal overload and magnetic fault Protection function alarm Monitoring function, indication of main motor parameters |
| Messages display capacity | 2 lines of 12 characters - display LCD - English - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - French - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - German - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - Italian - accuracy +/- 5 % - resolution 1 % of Ir 2 lines of 12 characters - display LCD - Spanish - accuracy +/- 5 % - resolution 1 % of Ir |
| Product specific application | Most sophisticated control and protection requirements, with display |
| Resistance to fast transients | 2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
| Resistance to radiated fields | 10 V/m 3 conforming to IEC 61000-4-3 |
| Immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
| Ambient air temperature for storage | -40...85 °C |
| Ambient air temperature for operation | -25...60 °C |
| Resistance to electrostatic discharge | 8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2 |
MPN