Schneider Electric LV525630
MPNLV525630
Active
Easypact CVS - CVS250F 6.2 250A circuit breaker - 4P
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Circuit breaker |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Height | 161 mm |
| Width | 140 mm |
| Depth | 86 mm |
| Parameter | Value |
|---|---|
| [In] rated current | 250 A at 40 °C |
| Breaking capacity | 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service breaking capacity | 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 32 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Parameter | Value |
|---|---|
| Poles description | 4P |
| Trip unit name | ETS 6.2 |
| Trip unit technology | Electronic |
| Device short name | CVS250F |
| Standards | IEC 60947-2 EN 60947-2 |
MPN
LV525630