Skip to main content
Schneider Electric LV964952

Schneider Electric LV964952

MPNLV964952
Active

Circuit breaker frame, MasterPacT MTZ2 08H1b, for MicroLogic Active, 800A, 85kA/440VAC (Icu), 3P, drawout

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV964952 key specifications
ParameterValue
Control typePush-button
Performance typeH1b 85 kA 440 V AC
Product or component typeCircuit breaker
Voltage1000 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage12 kV
[Icw] rated short-time withstand current85 kA 1 s
Current800 A at 40 °C
[Icm] rated short-circuit making capacity187 kA 220/415 V AC at 50/60 Hz 187 kA 440 V AC at 50/60 Hz 187 kA 525 V AC at 50/60 Hz 187 kA 690 V AC at 50/60 Hz
[Ics] rated service short-circuit breaking capacity85 kA at 220/415 V AC 50/60 Hz 85 kA at 440 V AC 50/60 Hz 85 kA at 525 V AC 50/60 Hz 85 kA at 690 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity85 kA at 220/415 V AC 50/60 Hz 85 kA at 440 V AC 50/60 Hz 85 kA at 525 V AC 50/60 Hz 85 kA at 690 V AC 50/60 Hz
Poles description3P

All specifications

LV964952 additional specifications
ParameterValue
IK degree of protectionIK07 conforming to EN/IEC 62262
IP degree of protectionIP3X conforming to EN/IEC 60529
Mounting modeDrawout
Mounting supportBase plate Rails
Connection pitch115 mm
Upside connectionFront Rear
Downside connectionFront Rear
Maximum closing response time70 ms
Pollution degree3 conforming to IEC 60664-1
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
DepthDrawout circuit breaker with chassis: 403 mm Drawout circuit breaker without chassis: 331 mm
WidthDrawout circuit breaker with chassis: 441 mm Drawout circuit breaker without chassis: 378 mm
HeightDrawout circuit breaker with chassis: 439 mm Drawout circuit breaker without chassis: 301 mm
Product weight90 kg
Electrical durability5000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 2500 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Mechanical durability20000 cycles with maintenance
StandardsEN/IEC 60947-1 EN/IEC 60947-2
RangeMasterPacT
Control unitWithout control unit
Sensor rating400 A 630 A 800 A
Device short nameMTZ2 08 H1b
Device applicationPower distribution protection
Selectivity categoryCategory B
Maximum breaking time25 ms
Suitability for isolationYes conforming to EN/IEC 60947-2
Temperature derating table40 °C ( 800 A ) 45 °C ( 800 A ) 50 °C ( 800 A ) 55 °C ( 800 A ) 60 °C ( 800 A ) 65 °C ( 800 A ) 70 °C ( 800 A )
Ambient air temperature for storage-40...85 °C
Ambient air temperature for operation-25...70 °C
MPN
LV964952