Multi9 - C60CTRL - MCB - 1P - 4 A - Z Curve - 240 V - 100 kA
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Control type | Toggle |
| Network type | DC AC |
| Product or component type | Miniature circuit-breaker |
| Voltage | 500 V AC 50/60 Hz EN/IEC 60947-2 |
| [Ue] rated operational voltage | 240 V AC 50/60 Hz between phase and neutral 60 V DC |
| [Uimp] rated impulse withstand voltage | 6 kVEN/IEC 60947-2 |
| Breaking capacity | 100 kA Icu 240 V AC 50/60 Hz EN/IEC 60947-2 25 kA Icu 60 V DC EN/IEC 60947-2 |
| Line rated current | 4 A |
| [Ics] rated service breaking capacity | 50 kA 50 % EN/IEC 60947-2 - 240 V AC 50/60 Hz 25 kA 100 % EN/IEC 60947-2 - 60 V DC |
| Network frequency | 50/60 Hz |
| Poles description | 1P |
| Number of protected poles | 1 |
All specifications
| Parameter | Value |
|---|---|
| Utilisation category | Category A EN/IEC 60947-2 |
| IP degree of protection | IP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529 |
| Mounting mode | Clip-on |
| Mounting support | DIN rail |
| Wire stripping length | 0.6 in (14 mm) for top or bottom connection |
| Connections - terminals | Tunnel type terminal top or bottom) 0.002...0.04 in² (1...25 mm²) - rigid Tunnel type terminal top or bottom) 0.002...0.04 in² (1...25 mm²) - flexible Tunnel type terminal top or bottom) 0.002...0.04 in² (1...25 mm²) - flexible with ferrule |
| Pollution degree | 3 EN/IEC 60947-2 |
| Relative humidity | 95 % 131 °F (55 °C) |
| Color | Gray |
| Depth | 2.8 in (72 mm) |
| Width | 0.7 in (18 mm) |
| Height | 3.2 in (81 mm) |
| Electrical durability | 10000 cycles |
| Mechanical durability | 20000 cycles |
| Standards | EN/IEC 60947-2 |
| Range | Multi9 |
| Curve code | Z |
| 9 mm pitches | 2 |
| Tropicalisation | 2 IEC 60068-1 |
| Local signalling | ON/OFF indication |
| Device short name | C60CTRL |
| Tightening torque | 17.7 lbf.in (2 N.m) top or bottom |
| Device application | Distribution |
| Trip unit technology | Thermal-magnetic |
| Magnetic tripping limit | 3 x In +/- 20 % AC 4.2 x In +/- 20 % DC |
| Earth-leakage protection | Separate block |
| Provision for padlocking | Padlockable |
| Suitability for isolation | Yes EN/IEC 60947-2 |
| Contact position indicator | Yes |
| Ambient air temperature for storage | -40...176 °F (-40...80 °C) |
| Ambient air temperature for operation | -22...158 °F (-30...70 °C) |
MPN