Skip to main content
Schneider Electric NHDF36050TW

Schneider Electric NHDF36050TW

MPNNHDF36050TW
Active

PowerPacT multistandard - H-Frame - 50 A - 25 KA - Therm-Mag trip unit

$325.12Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NHDF36050TW key specifications
ParameterValue
Control typeToggle
Display type3 LEDs
Range of productPowerPact multistandard
Product or component typeCircuit breaker
Long time pick-up adjustment type irFixed
Short-time pick-up adjustment type isdFixed
Voltage750 V AC 50/60 Hz IEC 60947-2
[Ue] rated operational voltage525 V AC 50/60 Hz IEC 60947-2 690 V AC 50/60 Hz IEC 947-2 600 V AC 50/60 Hz UL 489
[Uimp] rated impulse withstand voltage8 kV IEC 60947-2
Breaking capacityIcu 25 kA 220/240 V - AC IEC 947-2 Icu 18 kA 380/415 V - AC IEC 947-2 Icu 18 kA 440/480 V - AC IEC 947-2 Icu 14 kA 500/525 V - AC IEC 947-2 25 kA 240 V - AC UL 489 18 kA 480 V - AC UL 489 14 kA 600 V - AC UL 489
Current50 A 104 °F (40 °C)
Breaking capacity codeHD

All specifications

NHDF36050TW additional specifications
ParameterValue
[Ics] rated service breaking capacityIcs 25 kA 220/240 V - AC IEC 947-2 Ics 18 kA 380/415 V - AC IEC 947-2 Ics 18 kA 440/480 V - AC IEC 947-2 Ics 14 kA 500/525 V - AC IEC 947-2
Poles description3P
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting modeUnit mount
Mounting supportDIN rail Flush Backplate
Connection pitch1.8 in (45 mm)
Electrical connectionTerminal nut, line side Terminal nut, load side
Pollution degree3 IEC 60947-1 3 IEC 60664-1
Depth3.4 in (86 mm)
Width4.09 in (104 mm)
Height6.4 in (163 mm)
Electrical durability4000 cycles
Mechanical durability4000 cycles
StandardsNMX J-266 IEC 60947-2 NEMA AB1 W-C-375B/GEN CSA C22.2 No 5 UL 489
RangePowerPact
Trip unit nameTM
Local signallingON/OFF indication
Trip unit rating50 A
Device short nameH-Frame
Device applicationDistribution
Overvoltage categoryII
Trip unit technologyThermal-magnetic
Provision for padlockingNon padlockable
Suitability for isolationYes
Contact position indicatorYes
Trip unit protection functionsBasic protection
Long time pick-up adjustment range1 In
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation104 °F (40 °C)
[Isd] short-time pick-up adjustment range850 A
MPN