NTSAHO0212H key specifications
ParameterValue
Type of cableShielded cable
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc)
Analogue output typeCurrent 4...20 mA
Output protection type30V over voltage for current output
Product or component typeAnalog HART output module
Rated operational voltage limits20.4...28.8 V DC
Typical current consumption37.4 mA 24 V DC on the Bus current 34.1 mA 24 V DC on the internal field current minimum 82.5 mA 24 V DC on the internal field current maximum
Power dissipation in2.3 W maximum at 24 V DC
Isolation between field power and bus1500 V AC
IP degree of protectionIP20
Mounting supportbase

All specifications

NTSAHO0212H additional specifications
ParameterValue
Maximum cable distance between devicesShielded cable <3280.8 ft (1000 m) current input
Response time on output500 µs at 8750 Ohm per module (HART disabled)
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth2.7 in (69 mm)
Width1.2 in (30 mm)
Height3.9 in (100 mm)
Housing colourGrey
Product weight0.174 lb(US) (0.079 kg)
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5 EN/IEC 61850-3 EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Non-linearity<= 0.02 % FS current
HART toleranceYes
Operating modeAsynchronous
Local signalling1 LED green module operating (RUN) 1 LED per channel green channel diagnostic 1 LED red module error (ERR)
Measurement error<= 0.2 % FS - 40...70 °C
Output diagnosticUnderflow error per channel Overflow error per channel Broken wire error per channel Short circuit error per channel Hardware error per channel Calibration error per channel DAC power error per channel Internal field power supply error per channel
Temperature drift± 0.002 % FS/ °C
Device applicationIndustrial application in severe environment
Output wiring mode2 wires
Mandatory accessoryNTSXBA0200H base NTSXTB12_0_H terminal block
Load impedance ohmic750 Ohm current
Protective treatmentConformal coating
Hot swapping fallbackYes
Analogue output number2
Isolation between channels530 V AC
Environmental characteristicGas resistant CX & GX combined C3 and G2 Salt spray resistant
Isolation between channels and bus1500 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation104...158 °F (40...70 °C)
Isolation between channels and field pwr1000 V AC