Specifications

RE17LHBM key specifications
ParameterValue
Control typeSelector switch front panel
Time delay typeH
Range of productHarmony Timer Relays
Discrete output typeSolid state
Product or component typeModular timing relay
Voltage drift+/- 0.2 %/V
Voltage range0.85...1.1 Us
Maximum voltage drop<8 V 2-wire
Release of input voltage9 V
Maximum switching voltage250 V AC
Supply voltage24...240 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage5 kV 1.2/50 µs

All specifications

RE17LHBM additional specifications
ParameterValue
Breaking capacity0.5 A AC UL 0.7 A AC 68 °F (20 °C)
Maximum output current20 A
Nominal output current0.7 A
Maximum leakage current5 mA
Minimum switching current10 mA
Power on delay100 ms
Power consumption in0...3 VA 240 V AC
Maximum power consumption in1.5 W 240 V DC
Supply frequency50...60 Hz +/- 5 %
Operating frequency10 Hz
IP degree of protectionIP20 IEC 60529 terminal block) IP40 IEC 60529 housing) IP50 IEC 60529 front panel)
Mounting support35 mm DIN rail conforming to IEC 60715
Mounting positionAny position in relation to normal vertical mounting plane
Connections - terminalsScrew terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Shock resistance15 gn 11 ms IEC 60068-2-27
Relative humidity93 % without condensation IEC 60068-2-30
Vibration resistance20 m/s² (f= 10...150 Hz) conforming to IEC 60068-2-6
Depth2.8 in (72 mm)
Width0.7 in (17.5 mm)
Height3.5 in (90 mm)
Housing materialPolycarbonate
Control signal pulse width0.05 s typical
Electrical durability100000000 cycles
Standards2006/95/EC IEC 61000-6-1 IEC 61000-6-3 IEC 61000-6-2 IEC 61812-1 IEC 61000-6-4 2004/108/EC
MarkingCE
CategoryUS10CP222370
Reset time350 ms on de-energisation typical
FunctionalityOn-delay timing
Component nameRE17L
On-load factor100 %
Derating factor5 mA/°C
Repeat accuracy+/- 0.5 % IEC 61812-1
Time delay range1...10 s 1...10 h 0.1...1 s 6...60 s 6...60 min 1...10 min 10...100 h
Creepage distance4 kV/3 IEC 60664-1
Temperature drift+/- 0.05 %/°C
Tightening torque5.3...8.9 lbf.in (0.6...1 N.m) IEC 60947-1
Compatibility codeRE17
Function availableH- Interval relay-1 solid state output
Dielectric strength2.5 kV 1 mA/1 minute 50 Hz IEC 61812-1
Number of functions1
Insulation resistance100 MOhm 500 V DC IEC 60664-1
Immunity to microbreaks20 ms
Safety reliability dataMTTFd = 353.8 years B10d = 320000
Electromagnetic compatibilityElectrostatic discharge immunity test 6 kV in contact) level 3 IEC 61000-4-2 Electrostatic discharge immunity test 8 kV in air) level 3 IEC 61000-4-2 Susceptibility to electromagnetic fields 10 V/m 80 MHz to 1 GHz) level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test 1 kV capacitive connecting clip) level 3 IEC 61000-4-4 Electrical fast transient/burst immunity test 2 kV direct) level 3 IEC 61000-4-4 1.2/50 µs shock waves immunity test 1 kV differential mode) level 3 IEC 61000-4-5 1.2/50 µs shock waves immunity test 2 kV common mode) level 3 IEC 61000-4-5 Conducted RF disturbances 10 V 0.15...80 MHz) level 3 IEC 61000-4-6 Voltage dips and interruptions immunity test 0 % 1 cycle) IEC 61000-4-11 Voltage dips and interruptions immunity test 70 % 25/30 cycles) IEC 61000-4-11 Conducted and radiated emissionsclass B EN 55022
Setting accuracy of time delay+/- 10 % of full scale 25 °C IEC 61812-1
Ambient air temperature for storage-22...140 °F (-30...60 °C)
Ambient air temperature for operation-4...140 °F (-20...60 °C)
MPN