Skip to main content
Schneider Electric RM17UB310

Schneider Electric RM17UB310

MPNRM17UB310
Active

HARMONY, MODULAR 3-PHASE VOLTAGE

$63.50Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

RM17UB310 key specifications
ParameterValue
TypeVoltage control relay
Control typeWithout test button
Range of productHarmony Control Relays
Product or component type3-phase control relay
Contacts type and composition1 C/O
Supply voltage limits183...528 V AC
Dielectric test voltage2 kV AC 50 Hz, 1 min
Maximum switching voltage250 V AC/DC
[Un] rated nominal voltage, self-powered
Voltage detection threshold183 V
Threshold adjustment voltage2...20 % of Un selected -2...-17 % in the range 220 V AC +2...+10 % in the range 480 V AC -2...-12 % in the range 208 V AC
Voltage400 V IEC 60664-1

All specifications

RM17UB310 additional specifications
ParameterValue
Nominal output current5 A
Maximum switching current5 A AC/DC
Minimum switching current10 mA 5 V DC
Delay at power up650 ms
Power consumption in0...22 VA 400 V AC 50 Hz
Control circuit frequency50...60 Hz +/- 10 %
Utilisation categoryAC-12 IEC 60947-5-1 AC-13 IEC 60947-5-1 AC-14 IEC 60947-5-1 AC-15 IEC 60947-5-1 DC-12 IEC 60947-5-1 DC-13 IEC 60947-5-1 DC-14 IEC 60947-5-1
IP degree of protectionIP20 IEC 60529 terminals) IP30 IEC 60529 casing)
Mounting support35 mm symmetrical DIN rail conforming to IEC 60715
Connections - terminalsScrew terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end Screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Response time< 200 ms (in the event of a fault)
Pollution degree3 IEC 60664-1
Shock resistance5 gn IEC 60068-2-27
Relative humidity95 % 131 °F (55 °C) IEC 60068-2-30
Vibration resistance0.35 mm (f= 5...57.6 Hz) conforming to IEC 60068-2-6 1 gn (f= 57.6...150 Hz) conforming to IEC 60255-21-1
Non-dissipating shock wave4 kV
Width0.7 in (17.5 mm)
Housing materialPolycarbonate
Electrical durability100000 cycles
Mechanical durability30000000 cycles
StandardsIEC 60255-1
CategoryUS10CP222380
Directives89/336/EEC - electromagnetic compatibility 73/23/EEC - low voltage directive
Hysteresis2 %
Relay nameRM17UB3
Reset time1500 ms time delay
Time delayAdjustable 0.3...30 s, 0 + 10 % Tt- time delay upon fault
Operating rate<= 360 operations/hour full load
Quality labelsCE
Output contacts1 C/O
Repeat accuracy+/- 0.5 % input and measurement circuit +/- 1 % time delay
Local signallingLED (green) for power ON LED (yellow) for relay ON
Measurement error< 1 % over the whole range with voltage variation 0.05 %/°C with temperature variation
Measurement range220...480 V AC
Tightening torque5.3...8.9 lbf.in (0.6...1 N.m) IEC 60947-1
Operating positionAny position without derating
Measurement accuracy+/- 10 % of the full scale value
Overvoltage categoryIII conforming to IEC 60664-1
Insulation resistance> 500 MOhm 500 V DC IEC 60255-5 > 500 MOhm 500 V DC IEC 60664-1
Maximum measuring cycle150 ms measurement cycle as true rms value
Safety reliability dataB10d = 470000 MTTFd = 502.2 years
Switching capacity in1250 VA
Relay monitored parametersOvervoltage and undervoltage between phases
Product specific applicationFor 3-phase supply
Electromagnetic compatibilityEmission standard for industrial environments conforming to IEC 61000-6-4 Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 Immunity for industrial environments conforming to NF EN/IEC 61000-6-2
Ambient air temperature for storage-40...158 °F (-40...70 °C)
Ambient air temperature for operation-4...122 °F (-20...50 °C)
MPN
RM17UB310