Schneider Electric TSXPAY262
MPNTSXPAY262
Obsolete
Preventa safety module, Modicon Premium, 19.2 to 30VDC, 30mA, 5W
$777.24Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Range of product | Modicon Premium Automation platform |
| Product or component type | Preventa safety module |
| Isolation voltage | 4000 V III 2 |
| Supply voltage limits | 19.2...30 V |
| Supply voltage | 24 V DC |
| [Ue] rated operational voltage | 17...127 V DC relay output 19...250 V AC relay output |
| Inrush current | 0.5 A |
| Current consumption | < 150 mA 5 V DC <= 200 mA 24 V DC |
| Minimum output current | 30 mA |
| Short-circuit protection | 1 A gG external IEC 947-5-1 on power supply 4 A gG external IEC 947-5-1 on safety relay outputs |
| [Ithe] conventional enclosed thermal current | 2.5 A |
| Rated power in | 120 VA 48 V AC-15 inductive 280 VA 110 V AC-15 inductive 550 VA 220 V AC-15 inductive 60 VA 24 V AC-15 inductive |
All specifications
| Parameter | Value |
|---|---|
| Maximum power dissipation in | 5 W |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Cable cross section | 0.0003...0.004 in² (0.2...2.5 mm²) without cable end safety output circuit 0.002 in² (1.5 mm²) with cable end safety output circuit |
| Electrical connection | 1 connector removable screw terminal block 6 pins for connecting the safety output 1 connector SUB-D 44 pins for connecting the safety system input |
| Response time on output | < 12 ms |
| Standards | EN 954 machine safety parts of control systems EN/IEC 60204-1 machine electrical equipment EN/IEC 61131-2 specific requirements (PLC) EN/ISO 12100 machine electrical equipment ISO 13850 emergency stop equipment UL 508 specific requirements (PLC) ISO 13849-1 category 4 machine safety parts of control systems IEC 61508 SIL 3 machine safety parts of control systems CSA C22.2 specific requirements (PLC) |
| Category | US1PC2222558 |
| Module format | Standard |
| Safety outputs | 2 NO safety relay AGCDO gold plated volt free output |
| Local signalling | 28 LEDs for diagnostic of safety system |
| Safety acquisition | Read feedback loop Monitor external power supply of the module Read enable inputs Read the safety outputs control Read status of the 24 inputs |
| Activation threshold | < 20 V |
| Discrete input logic | Positive |
| Discrete input number | 1 double or single contact selection input IEC 1131 Type 1 1 feedback loop input IEC 1131 Type 1 1 reset PB input IEC 1131 Type 1 1 reset PB monitoring input IEC 1131 Type 1 12 emergency stop or limit switch discrete inputs IEC 1131 Type 1 |
| Isolation between input and earth | 500 Vrms 50/60 Hz 60 s |
| Isolation between output and earth | 300 V DIN VDE 0110 part 2 1500 Vrms 50/60 Hz 60 s |
| Ambient air temperature for storage | -13...158 °F (-25...70 °C) |
| Ambient air temperature for operation | 32...104 °F (0...40 °C) without fan 32...140 °F (0...60 °C) with fan module |
MPN