Specifications

A9R40425 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)30 mA
Earth-leakage protection class / typeType AC
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9R40425 — Electrical Ratings
ParameterValue
Rated current (In)25 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)440 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)4 kV
Device location in systemOutgoer
Electrical durabilityAC-1: 2000 cycles
Mechanical durability (operating cycles)5000 cycles
A9R40425 — Identification
ParameterValue
Product nameActi9 iID K
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID K
A9R40425 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsTunnel type terminals top or bottom 1...35 mm² rigid Tunnel type terminals top or bottom 1...25 mm² flexible Tunnel type terminals top or bottom 1...25 mm² flexible with ferrule
Wire stripping length16 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height85 mm
Depth69 mm
A9R40425 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree2
A9R40425 — Approvals
ParameterValue
StandardsEN/IEC 61008-1

Product details

The Schneider Electric A9R40425 is an Acti9 iID K residual current circuit breaker (RCCB) — a 4-pole device rated for 25 A continuous current with a 30 mA earth-leakage sensitivity.

The 30 mA sensitivity is the standard for personal protection against indirect contact in TN and TT systems — it will trip on leakage currents above that threshold instantaneously (no intentional time delay). Breaking and making capacity is 500 A (Idm and Im), adequate for most final-circuit faults in a domestic or light commercial outgoer position. The insulation voltage rating is 440 V AC, and the pollution degree is 2 (normal, non-conductive pollution only). That means it is intended for clean indoor panels — not for outdoor enclosures or environments with condensation or conductive dust without additional enclosure protection. The IP20 body rating (IP40 with modular enclosure) confirms this: it is a panel-mount device, not a standalone outdoor unit.

Strip length is 16 mm; tighten to 3.5 N.m top or bottom. The toggle control gives a clear on/off position, though there is no separate contact position indicator. A padlocking device can be fitted for lockout/tagout. The 8-module width (72 mm) means it takes up a standard chunk of DIN rail — plan your enclosure fill factor accordingly. The electrical durability is 2000 cycles under AC-1 resistive load, and mechanical durability is 5000 cycles — fine for a distribution board that sees infrequent switching, but not rated for daily operational switching duty.

Frequently asked questions

How do I get pricing and availability for A9R40425?

Submit an RFQ through the storefront. The part is sourced to order against a quote; availability and current pricing are confirmed at that time.

What is the closest alternative to A9R40425 in the Acti9 family?

Within the same Acti9 iID range, the primary differentiator is the sensitivity and pole count. This 4P 30 mA Type AC unit is the standard choice for three-phase final circuits needing personal protection. A 100 mA or 300 mA variant would be used for fire protection or equipment protection instead, and a Type A or Type B variant would be needed if the load generates pulsed or smooth DC leakage.

What compliance documentation does Schneider provide for A9R40425?

The part is certified to EN/IEC 61008-1 and carries a VDE quality label. Standard Schneider documentation includes the declaration of conformity covering the applicable EU directives.

MPN
A9R40425