The Schneider Electric A9Z11463 is an Acti9 iID 4-pole residual current circuit breaker (RCCB) rated for 63 A continuous current with 30 mA earth-leakage sensitivity, Type AC (sinusoidal AC residual currents only). The 30 mA sensitivity is the standard threshold for personal protection against indirect contact in residential and commercial final circuits (EN/IEC 61008-1).
Key ratings and installation constraints
The RCCB is voltage-independent for residual current tripping — it detects leakage without needing a separate power supply, which simplifies wiring in retrofit panels. Tripping is instantaneous (no time delay), so it cannot be used for selectivity with downstream RCCBs unless they are time-delayed type S. The 4-pole unit (3 phases + neutral, neutral on the left) occupies 8 x 9 mm pitches (72 mm wide).
Durability and environmental range
Rated for 20,000 mechanical cycles and 15,000 electrical cycles under AC-1 resistive load. The 6 kV rated impulse withstand voltage (Uimp) covers typical transient overvoltages in low-voltage installations. The 8/20 µs impulse withstand of 250 A ensures the RCCB does not nuisance-trip on common surge events.