Skip to main content
Schneider Electric A9Z26440 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric A9Z26440 Acti9 iID RCCB, 40A 4P 500mA Typ

MPNA9Z26440
Active

Schneider Electric Acti9 iID, 4P RCCB, 40 A, 500 mA Type A, 380–415 V AC, DIN rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

A9Z26440 — Residual Current Protection
ParameterValue
Earth-leakage sensitivity (IΔn)500 mA
Earth-leakage protection class / typeType A
Earth-leakage trip time delayInstantaneous
Residual-current tripping technologyVoltage independent
A9Z26440 — Electrical Ratings
ParameterValue
Rated current (In)40 A
Rated operational voltage (Ue)380...415 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)6 kV
Electrical durabilityAC-1: 15000 cycles
Mechanical durability (operating cycles)20000 cycles
A9Z26440 — Identification
ParameterValue
Product nameActi9 iID
Product / component typeResidual current circuit breaker (RCCB)
Product range / familyActi9
Device short nameiID
A9Z26440 — Mechanical
ParameterValue
Mounting supportDIN rail
Mounting modeClip-on
Control typeToggle
Width in 9 mm modules8
Terminal connectionsDouble terminal front 1...35 mm² rigid Double terminal front 1...25 mm² flexible Double terminal front 1...25 mm² flexible with ferrule Double terminal back 1...25 mm² rigid Double terminal back 1...16 mm² flexible Double terminal back 1...16 mm² flexible with ferrule
Wire stripping length14 mm for top or bottom connection
Terminal tightening torque3.5 N.m top or bottom
Width72 mm
Height91 mm
Depth73 mm
A9Z26440 — Environmental
ParameterValue
Operating ambient temperature-25...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529 IP40 (modular enclosure) conforming to IEC 60529
Pollution degree3
A9Z26440 — Approvals
ParameterValue
StandardsEN/IEC 61008-1 EN/IEC 61008-2-1

Product details

Breaking capacity is rated at Idm 1500 A / Im 1500 A, with a conditional short-circuit current of 10 kA when backed by an upstream overcurrent device. That means the RCCB itself handles fault currents up to 1500 A and can be installed on networks with prospective short-circuit currents up to 10 kA, provided the upstream MCB or fuse clears the fault. The 6 kV rated impulse withstand voltage (Uimp) and pollution degree 3 suit industrial panel environments where transient surges and conductive dust are present.

IP20 finger protection on the terminals, IP40 on the modular enclosure — standard for enclosed distribution boards.

Type A earth-leakage protection class covers AC and pulsating DC faults. The 8/20 µs impulse withstand test (250 A) confirms electromagnetic compatibility with surge events on the mains. Storage temperature range -40…85 °C, operating -25…60 °C.

Frequently asked questions

Where can I buy the A9Z26440 and how do I get a price?

The A9Z26440 is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — no stock count or price is published here, but the part is a standard active line and can be procured.

What is the A9Z26440's rated sensitivity and protection type?

500 mA earth-leakage sensitivity, Type A — covers sinusoidal AC and pulsating DC fault currents. Instantaneous trip, voltage-independent residual current detection.

What standards does the A9Z26440 comply with?

EN/IEC 61008-1 and EN/IEC 61008-2-1. The impulse withstand is 8/20 µs, 250 A. Pollution degree 3, rated insulation voltage 500 V AC.

MPN
A9Z26440