Breaking capacity is rated at Idm 1500 A / Im 1500 A, with a conditional short-circuit current of 10 kA when backed by an upstream overcurrent device. That means the RCCB itself handles fault currents up to 1500 A and can be installed on networks with prospective short-circuit currents up to 10 kA, provided the upstream MCB or fuse clears the fault. The 6 kV rated impulse withstand voltage (Uimp) and pollution degree 3 suit industrial panel environments where transient surges and conductive dust are present.
IP20 finger protection on the terminals, IP40 on the modular enclosure — standard for enclosed distribution boards.
Type A earth-leakage protection class covers AC and pulsating DC faults. The 8/20 µs impulse withstand test (250 A) confirms electromagnetic compatibility with surge events on the mains. Storage temperature range -40…85 °C, operating -25…60 °C.