Skip to main content
Schneider Electric C080H4FM — Miniature Circuit Breakers (MCB)

C080H4FM ComPacT NS800H Basic Frame, 800A 4P Fixed, 70kA 415

MPNC080H4FM
Active

Schneider Electric ComPacT NS800H new generation, basic frame, 800 A at 50 °C, 4 poles, fixed, manually operated, 70 kA Icu at 415 V AC, IEC 60947-2.

$1,392.64 – $1,907.04Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080H4FM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C080H4FM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C080H4FM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C080H4FM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
C080H4FM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C080H4FM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The C080H4FM is a basic frame — no electronic trip unit included — from the ComPacT NS630b...1600 new generation range. Rated 800 A at 50 °C, it is sized for main or feeder distribution in a fixed, backplate-mounted installation with 4 poles (neutral left). The 70 kA Icu at 415 V AC (85 kA at 240 V) places it in the H breaking-capacity class, meaning it can interrupt fault currents up to that level without upstream cascading failure, per IEC 60947-2. Because it ships without protection, the buyer must pair it with a compatible trip unit (e.g., Micrologic) to define the overcurrent curve; this frame alone is a mechanical switch with integral instantaneous protection set at 40 kA.

Fixed mounting on a backplate, 280 mm wide × 224 mm high × 147 mm deep. Connection pitch is 70 mm. The 4-pole arrangement places the neutral on the left. IP40 front face (IK07 impact resistance) suits it for enclosed panel installation where splash or tool contact is minimal — not for washdown environments.

Approvals and compliance documentation

Designed to IEC 60947-2, with suitability for isolation (EN/IEC 60947-2). The front face carries Class II shock protection. Overvoltage category III, rated impulse withstand 8 kV. The standard compliance package includes the IEC 60947-2 declaration; for specific RoHS/REACH/UL documentation, the manufacturer's product compliance portal should be consulted — this listing does not carry those certificates on file.

Frequently asked questions

What is the breaking capacity of C080H4FM at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, with an Ics (service breaking capacity) of 50 kA at the same voltage.

Does C080H4FM include a trip unit?

No — this is a basic frame without protection. It must be paired with a separate trip unit (e.g., Micrologic) to set overcurrent protection.

Where can I buy C080H4FM and how is it quoted?

It is sourced to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
C080H4FM