Schneider Electric C080N4WM — Miniature Circuit Breakers (MCB)

Schneider Electric C080N4WM ComPacT NS800N, 800A, 4P Drawout

MPNC080N4WM
Active

Schneider Electric ComPacT NS800N new generation, basic frame C080N4WM, 800 A, 4P, withdrawable, manually operated, 50 kA at 415 V AC.

$746.75Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C080N4WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C080N4WM — Ratings
ParameterValue
Rated current (In)800 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C080N4WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 4000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 6000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C080N4WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C080N4WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C080N4WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

ComPacT NS800N basic frame — what you're sourcing

It carries an 800 A rated current at 50 °C across 4 poles, with a withdrawable (drawout) mounting style and manual operation. The breaking capacity hits 85 kA Icu at 220/240 V AC and 50 kA Icu at 380/415 V AC, both per IEC 60947-2.

The 800 A rating at 50 °C means this frame is sized for a main or heavy feeder in a 480 V or 400 V distribution board — think a 500 kVA transformer secondary or a large motor control center bus. Withdrawable mounting means the chassis pulls out for inspection or swap without unbolting bus bars — a real time-saver on a live panel if the line's down and you need to rack in a spare. The frame is isolation-rated per EN/IEC 60947-2 — it provides visible isolation when racked out, which satisfies lockout/tagout requirements without a separate disconnect switch.

Mounts on a backplate with a 70 mm connection pitch. The 306 mm width, 260 mm height, and 147 mm depth are the envelope for the drawout chassis — make sure your cabinet has enough depth for the racking mechanism and clearance for the manual operator on the front face. Neutral is on the left, which matters if your bus bar layout is handed. The 30 W power loss is continuous at rated current — factor that into your enclosure ventilation calculation to keep ambient below the 70 °C operating max.

Frequently asked questions

What is the breaking capacity of C080N4WM at 415 V?

50 kA Icu at 380/415 V AC, 50/60 Hz, per IEC 60947-2. The Ics (service breaking capacity) is also 50 kA at the same voltage, so it can reclose after clearing a fault at that level.

What does C080N4WM include?

It is a basic frame — the bare chassis with manual operator, withdrawable mechanism, and 4 poles rated 800 A. It ships without a trip unit or protection module; you add a separate Micrologic control unit to set the protection curves.

MPN
C080N4WM