Skip to main content
Schneider Electric C10S2TM030 — Miniature Circuit Breakers (MCB)

Schneider Electric C10S2TM030 ComPacT NSX Circuit Breaker, 3

MPNC10S2TM030
Active

Schneider Electric ComPacT NSX, C10S2TM030, 2-pole circuit breaker, 30 A rated current, thermal-magnetic TM-D trip unit, 70 kA breaking capacity at 415 V AC, IP40.

$4.14Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10S2TM030 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10S2TM030 — Ratings
ParameterValue
Rated current (In)30 A at 40 °C
Poles configuration2P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 250 V DC 1 pole conforming to IEC 60947-2 100 kA Icu at 500 V DC 2 poles in series conforming to IEC 60947-2 100 kA Icu at 500 V DC 2P conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 250 V DC conforming to IEC 60947-2 100 kA at 500 V DC conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz 500 V DC
Rated insulation voltage (Ui)750 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC DC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10S2TM030 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 277 V In/2 10000 cycles at 277 V In
Mechanical durability (cycles)20000 cycles
C10S2TM030 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10S2TM030 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10S2TM030 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10S2TM030 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The C10S2TM030 is a Schneider Electric ComPacT NSX100S circuit breaker — a 2-pole, fixed-mount thermal-magnetic breaker rated 30 A at 40 °C. This is a Category A breaker (no intentional short-time delay), designed for distribution duty — not motor starting or high-inductive switching. It's built to EN/IEC 60947-2, so it's suitable for isolation (the standard requires the open contacts to visibly disconnect the load). The TM-D trip unit uses a thermal bimetal for overload protection (L) and a magnetic coil for short-circuit protection (I). That's the standard thermal-magnetic pairing — no electronic adjustments, no earth-leakage module on this variant.

Breaking capacity — what the S rating means for your panel

That's the highest available for the NSX100 frame at that voltage — the standard F and N ratings top out lower. At 220/240 V AC it jumps to 100 kA Icu; at 690 V AC it still holds 10 kA Icu. For DC applications, it delivers 100 kA Icu at 250 V DC (1-pole) and 500 V DC (2 poles in series). If you're on a 50 kA system, the F-rating would suffice — but the S gives you margin for future upgrades or utility changes without swapping the breaker.

Mounts flat on a backplate (DIN-rail adapter available separately if you need it). Fixed-mount, 2-pole, 70 mm wide, 161 mm tall, 86 mm deep. Front connections both top and bottom — standard for panel wiring with busbars or cable lugs. IP40 enclosure protection keeps dust and accidental contact out; IK07 impact resistance handles the occasional dropped tool in a panel. Horizontal or vertical mounting position, flat on the back.

Durability and thermal performance

Mechanical durability is 20,000 cycles; electrical durability is 20,000 cycles at 277 V at half rated current, and 10,000 cycles at full rated current. Power dissipation is 4.03 W per pole — relevant for panel heat calculations when you're stacking multiple breakers in a closed enclosure.

Frequently asked questions

Where can I buy C10S2TM030?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time figure is published here.

What is C10S2TM030's breaking capacity at 415 V AC?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. That's the S rating on the NSX100S frame, which is the highest available for this frame size at that voltage.

What standards does C10S2TM030 comply with?

It complies with EN/IEC 60947-2, which covers low-voltage switchgear and controlgear for circuit breakers. It is suitable for isolation per that standard, and carries IP40 and IK07 protection ratings.

MPN
C10S2TM030