The C12H3TM125L is a 3-pole ComPacT NSXm circuit breaker with a 125 A thermal-magnetic trip unit (TM-D) rated at 40 °C. The thermal-magnetic trip gives you an inverse-time curve for overloads plus instantaneous magnetic protection for short circuits, so it handles both motor-start inrush and distribution feeder duty in one device.
Mounts flat on a backplate in horizontal or vertical orientation — no DIN-rail adapter needed. The front-facing terminals accept Everlink lugs for 2.5–70 mm² flexible copper or 2.5–95 mm² rigid/stranded copper, with a 35 mm connection pitch (27 mm without spreaders). The 9-module pitch (81 mm wide, 137 mm high, 80 mm deep) fits standard distribution board cutouts.