Skip to main content
Schneider Electric C25F42D160 — Miniature Circuit Breakers (MCB)

C25F42D160 ComPacT NSX 160A 4P MCCB, 85 kA at 240V

MPNC25F42D160
Active

Schneider Electric ComPacT NSX NSX250F, 160 A at 40 °C, 4-pole MCCB with MicroLogic 2.2 electronic trip unit, 85 kA Icu at 240 V AC, toggle control.

$629.35 – $1,748.52Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F42D160 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25F42D160 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25F42D160 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25F42D160 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25F42D160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25F42D160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25F42D160 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range63...160 A
Trip unit protection functionsLSoI

Product details

The C25F42D160 is a Schneider Electric ComPacT NSX moulded-case circuit breaker, frame size NSX250F, rated 160 A at 40 °C in a 4-pole configuration. The MicroLogic 2.2 electronic trip unit provides LSI protection — long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). That means you get adjustable overload pickup and time delay plus a fixed short-time delay for selective coordination downstream, then instantaneous clearing for hard faults. Breaking capacity is 85 kA Icu at 240 V AC and 36 kA at 415 V AC per IEC 60947-2, with UL 60947-4-1 ratings of 85 kA at 240 V and 35 kA at 480 V. For a 160 A distribution breaker in a 480 V panel, the 35 kA SCCR gives real headroom for high-fault service entrances or transformer-secondaries. That matters for motor-starting or cyclic loads where nuisance trips on reclose are a risk.

The 4-pole unit with neutral on the left takes up a 140 mm width in the enclosure; plan your gland-plate layout and phase barrier clearance accordingly. Front connections both top and bottom. Connection pitch is 35 mm, which matches standard busbar and cable-lug spacing. Five accessory slots available for auxiliary contacts, shunt trips, or under-voltage releases. No earth-leakage module fitted on this variant — the MicroLogic 2.2 is a straight LSI trip without ground-fault sensing.

Compliant with EN/IEC 60947-2 for circuit-breaker performance and safety. Operating altitude 0–2000 m without derating, up to 5000 m with derating. Electrical durability is 20,000 cycles at 440 V at half rated current, 10,000 cycles at full rated current. That is typical for a distribution-grade MCCB — not a switching device for frequent motor starts, but fine for infrequent isolation and backup protection.

Frequently asked questions

What is the breaking capacity of C25F42D160?

85 kA Icu at 240 V AC, 36 kA at 415 V AC, 35 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, and 8 kA at 690 V, all per IEC 60947-2. UL ratings are 85 kA at 240 V, 35 kA at 480 V, and 15 kA at 600 V per UL 60947-4-1.

What trip unit does C25F42D160 use?

It uses a MicroLogic 2.2 electronic trip unit with LSI protection: long-time overload (L), short-time short-circuit with fixed delay (So), and instantaneous short-circuit (I). Rated 160 A at 40 °C.

What compliance documentation does C25F42D160 carry?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. It carries an IP40 enclosure rating per IEC 60529 and IK07 impact rating per IEC 62262. Pollution degree 3 per IEC 60664-1 and overvoltage category III.

MPN
C25F42D160