Skip to main content
Schneider Electric C40H3TM400 — Miniature Circuit Breakers (MCB)

Schneider Electric C40H3TM400 ComPacT NSX400H, 400 A, 70 kA

MPNC40H3TM400
Active

Schneider Electric ComPacT NSX400H, C40H3TM400, 3-pole thermal-magnetic circuit breaker, 400 A rated current, 70 kA Icu at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40H3TM400 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C40H3TM400 — Ratings
ParameterValue
Rated current (In)400 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40H3TM400 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C40H3TM400 — Mechanical
ParameterValue
Mounting supportBackplate DIN rail
Control typeToggle
Contact position indicatorYes
C40H3TM400 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40H3TM400 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40H3TM400 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In

Product details

The Schneider Electric C40H3TM400 is a ComPacT NSX400H 3-pole circuit breaker with a TM-D thermal-magnetic trip unit rated 400 A at 40 °C. Its breaking capacity hits 70 kA Icu at 380/415 V AC 50/60 Hz per EN/IEC 60947-2, and 100 kA Icu at 220/240 V AC — enough for high-fault utility feeds or transformer secondaries. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection in one block, no add-on electronic module needed.

At 690 V AC the Icu drops to 20 kA, so verify your system voltage against the full curve. Pollution degree 3 (IEC 60664-1) means it's rated for conductive pollution in industrial enclosures — no extra conformal coating needed inside a standard IP40 panel. Mechanical durability is 15,000 cycles, electrical durability 12,000 cycles at 440 V at half rated current (In/2) and 6,000 cycles at full In. That's typical for a distribution breaker — not a motor-switching duty cycle, but fine for infrequent manual isolation or backup protection.

Mounts on a backplate or DIN rail, horizontally or vertically, flat on the back. Front connections top and bottom — busbar or cable entry is straightforward in a standard distribution panel. The toggle handle gives clear contact position indication (open/closed/tripped).

The C40H3TM400 is current production per Schneider. It is part of the ComPacT NSX family.

Frequently asked questions

What is the breaking capacity of C40H3TM400 at 415 V?

70 kA Icu at 380/415 V AC 50/60 Hz per EN/IEC 60947-2, which is the H breaking capacity code.

What trip unit does C40H3TM400 use?

A TM-D thermal-magnetic trip unit rated 400 A at 40 °C, providing L (thermal overload) and I (magnetic short-circuit) protection.

What standards does C40H3TM400 comply with?

It complies with EN/IEC 60947-2 for circuit-breaker performance and safety, and is suitable for isolation per that standard.

MPN