That 36 kA at 415 V is the number to check against your upstream transformer and system fault level; the breaker also carries 40 kA at 240 V, 30 kA at 440 V, and 20 kA at 525 V, all per EN/IEC 60947-2. The 3-pole (3P) configuration and Category A utilisation class mean this breaker is designed for distribution duty — not for direct motor switching under load.
The 45 mm connection pitch and 6 accessory slots leave room for shunt trips, auxiliary contacts, or motor mechanisms without reworking the panel layout. IP40 enclosure rating keeps out tools and fingers but not washdown — install inside a cabinet. Operates in any orientation (horizontal, vertical, flat on back). Derate above 2000 m altitude; no derating needed below that. Ambient relative humidity up to 95 % is within spec.