Skip to main content
Schneider Electric C40N42D250 — Miniature Circuit Breakers (MCB)

Schneider Electric C40N42D250 ComPacT NSX 250A 4P 50kA 415V

MPNC40N42D250
Active

Schneider Electric ComPacT NSX, C40N42D250, 250 A, 4P, MicroLogic 2.3 electronic trip unit, 50 kA Icu at 415 V AC.

$1,042.82Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C40N42D250 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C40N42D250 — Ratings
ParameterValue
Rated current (In)250 A at 40 °C
Poles configuration4P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 42 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40N42D250 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C40N42D250 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40N42D250 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40N42D250 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40N42D250 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range70...250 A
Trip unit protection functionsLSoI

Product details

What this 250 A breaker brings to the panel

The C40N42D250 is a ComPacT NSX400N frame circuit breaker from Schneider Electric, rated 250 A at 40 °C with a MicroLogic 2.3 electronic trip unit. It's a 4-pole (4P) device built to EN/IEC 60947-2, with a breaking capacity code of N — 50 kA Icu at 415 V AC. That N rating means it handles the high fault currents common in industrial distribution panels without cascading upstream, so you don't oversize the main breaker just to protect a feeder.

Trip unit and protection: what the MicroLogic 2.3 actually does

The MicroLogic 2.3 provides three protection functions: L for overload (long-time), So for short-time short-circuit with a fixed delay, and I for instantaneous short-circuit. That fixed-delay So is the key differentiator — it lets you coordinate downstream breakers without nuisance tripping on transient faults. That's a real help on motor-starting circuits where repeated overloads can cook the cable before the bimetal catches up.

This breaker delivers 85 kA Icu at 240 V AC, 50 kA at 415 V, 42 kA at 440 V, 30 kA at 500 V, 22 kA at 525 V, and 10 kA at 690 V — all per IEC 60947-2. The UL ratings track similarly: 85 kA at 240 V, 50 kA at 480 V, and 20 kA at 600 V per UL 60947-4-1.

Mounting and integration in the panel

Dimensions are 255 mm high, 185 mm wide, 110 mm deep. IK07 impact rating means it survives a dropped tool without cracking the housing.

Frequently asked questions

What is the breaking capacity of C40N42D250 at 415 V?

The C40N42D250 has a breaking capacity code of N, delivering 50 kA Icu at 415 V AC per IEC 60947-2. That's the rating you'll see on the nameplate and the one that governs its use in most European industrial panels.

What protection functions does the MicroLogic 2.3 trip unit provide?

The MicroLogic 2.3 provides three protection functions: L for overload (long-time), So for short-time short-circuit with fixed delay, and I for instantaneous short-circuit. The So function with fixed delay is what enables selective coordination with downstream breakers.

MPN