Schneider Electric C40S4TM250D — Miniature Circuit Breakers (MCB)

Schneider Electric C40S4TM250D ComPacT NSX DC 250A 100kA Cir

MPNC40S4TM250D
Active

Schneider Electric ComPacT NSX DC, circuit breaker, 4P, 250 A, 100 kA Icu at 500 V DC, thermal-magnetic TM-DC trip unit, EN/IEC 60947-2.

$2,195.77Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40S4TM250D — Identification
ParameterValue
Product nameComPacT NSX DC
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C40S4TM250D — Ratings
ParameterValue
Rated current (In)250 A at 40 °C
Poles configuration4P
Breaking capacity100 kA Icu at 24...125 V DC 1 pole conforming to IEC 60947-2 100 kA Icu at 250 V DC 1 pole conforming to IEC 60947-2 100 kA Icu at 500 V DC 2 poles in series conforming to IEC 60947-2 100 kA Icu at 750 V DC 3 poles in series conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 24...125 V DC conforming to IEC 60947-2 100 kA at 250 V DC conforming to IEC 60947-2 100 kA at 500 V DC conforming to IEC 60947-2 100 kA at 750 V DC conforming to IEC 60947-2
Rated operational voltage (Ue)750 V DC
Rated insulation voltage (Ui)750 V DC conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)DC
Utilisation categoryCategory A
C40S4TM250D — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)2000 cycles at 750 V In/2 1000 cycles at 750 V In
Mechanical durability (cycles)5000 cycles
C40S4TM250D — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C40S4TM250D — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40S4TM250D — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40S4TM250D — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It's built for DC distribution panels where you need reliable overload and short-circuit protection on a 750 V DC bus. Breaking capacity is 100 kA Icu at 500 V DC (2 poles in series) per IEC 60947-2. The TM-DC trip unit gives you LI protection: thermal for overload (L) and magnetic for short-circuit (I). No earth-leakage built in — you'd add a Vigi module separately if that's needed. It's rated Category A (no intentional short-time delay), so it trips fast on a hard fault.

Mounts on a backplate — fixed, not plug-in. Front connections both top and bottom, with a 45 mm pole pitch. At 255 mm high, 185 mm wide, and 110 mm deep, it'll fit most standard enclosures, but watch the gland plate clearance — the front terminals need room for cable bending radius.

Frequently asked questions

What is the breaking capacity of the C40S4TM250D?

It offers 100 kA Icu at 500 V DC (2 poles in series) per IEC 60947-2, and the same 100 kA at 250 V DC (1 pole) and 750 V DC (3 poles in series).

What compliance documentation does Schneider provide for C40S4TM250D?

The breaker is certified to EN/IEC 60947-2 and carries IEC 60664-1 pollution degree 3 rating. It is suitable for isolation per that standard. For specific RoHS, REACH, or UL declarations, the documentation is available on request with your RFQ.