Skip to main content
Schneider Electric C40W32D250 — Miniature Circuit Breakers (MCB)

Schneider C40W32D250 ComPacT NSX 250A 3P 100kA 690V

MPNC40W32D250
Active

Schneider Electric ComPacT NSX, C40W32D250, 3P 250 A circuit breaker with MicroLogic 2.3 electronic trip unit, 100 kA Icu at 690 V AC, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C40W32D250 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C40W32D250 — Ratings
ParameterValue
Rated current (In)250 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C40W32D250 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)12000 cycles at 440 V In/2 6000 cycles at 440 V In 6000 cycles at 690 V In/2 3000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C40W32D250 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C40W32D250 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C40W32D250 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C40W32D250 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range70...250 A
Trip unit protection functionsLSoI

Product details

It carries a MicroLogic 2.3 electronic trip unit with L, So, and I protection curves — overload (long time), short-time short-circuit with fixed delay, and instantaneous short-circuit. Breaking capacity is 100 kA Icu at 500 V, 525 V, and 660/690 V AC 50/60 Hz per IEC 60947-2. That is the HB2 rating — full 100 kA up to 690 V.

Connection pitch is 45 mm. Front connections both upside and downside. IP40 enclosure protection, IK07 impact resistance. That means it is rated for industrial environments inside a panel — not outdoor or washdown, but fine for a typical MCC or distribution board.

Certified to EN/IEC 60947-2. Suitability for isolation is confirmed per that standard. IP40, IK07.

Frequently asked questions

What is the closest alternative to C40W32D250 in the ComPacT NSX family?

The closest sibling is the same NSX400HB2 frame with a different trip unit rating or MicroLogic variant. No pin-compatible alternative exists outside the ComPacT NSX range; the mounting footprint and connection pitch are specific to this series.

What is C40W32D250's breaking capacity at 690 V?

100 kA Icu at 660/690 V AC 50/60 Hz per IEC 60947-2 — the HB2 rating holds full capacity at the highest voltage.

What compliance documentation does Schneider provide for C40W32D250?

Declaration of conformity to EN/IEC 60947-2, test reports for type tests per that standard. Standard Schneider documentation package available on request.

MPN
C40W32D250