It carries a MicroLogic 2.3 electronic trip unit with L, So, and I protection curves — overload (long time), short-time short-circuit with fixed delay, and instantaneous short-circuit. Breaking capacity is 100 kA Icu at 500 V, 525 V, and 660/690 V AC 50/60 Hz per IEC 60947-2. That is the HB2 rating — full 100 kA up to 690 V.
Connection pitch is 45 mm. Front connections both upside and downside. IP40 enclosure protection, IK07 impact resistance. That means it is rated for industrial environments inside a panel — not outdoor or washdown, but fine for a typical MCC or distribution board.
Certified to EN/IEC 60947-2. Suitability for isolation is confirmed per that standard. IP40, IK07.