Skip to main content
Schneider Electric C63H3TM630 — Miniature Circuit Breakers (MCB)

C63H3TM630 ComPacT NSX630H 600A 3P MCCB, 70kA 415V

MPNC63H3TM630
Active

Schneider Electric ComPacT NSX series, C63H3TM630, 3-pole MCCB, 600 A rated, TM-D thermal-magnetic trip unit, H breaking capacity 70 kA at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C63H3TM630 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C63H3TM630 — Ratings
ParameterValue
Rated current (In)600 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to EN/IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 11 kA at 525 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C63H3TM630 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 440 V In/2 4000 cycles at 440 V In 6000 cycles at 690 V In/2 2000 cycles at 690 V In
Mechanical durability (cycles)15000 cycles
C63H3TM630 — Mechanical
ParameterValue
Mounting supportBackplate DIN rail
Control typeToggle
Contact position indicatorYes
C63H3TM630 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C63H3TM630 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C63H3TM630 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In

Product details

The C63H3TM630 is a Schneider Electric ComPacT NSX630H moulded-case circuit breaker, 3-pole, rated 600 A at 40 °C with a TM-D thermal-magnetic trip unit. The toggle-operated breaker mounts on a backplate or DIN rail, with front connections top and bottom.

The H rating delivers 70 kA Icu at 380/415 V AC, 65 kA at 440 V, and 35 kA at 525 V. At 220/240 V it reaches 100 kA Icu. For a 415 V distribution board fed from a transformer in the 1–2 MVA range, 70 kA gives real selectivity headroom downstream.

Thermal element tracks the 600 A rating at 40 °C; magnetic pickup is fixed. No earth-leakage module is integrated — that's a separate add-on slot if needed.

Six accessory slots are available for shunt trips, auxiliary contacts, or communication modules. Connection pitch is 45 mm. IP40 enclosure protection, IK07 impact resistance.

Frequently asked questions

Where can I buy C63H3TM630 and what is the lead time?

The part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What is C63H3TM630's breaking capacity at 415 V?

70 kA Icu at 380/415 V AC per EN/IEC 60947-2. At 440 V it is 65 kA, at 500 V 50 kA, and at 690 V 20 kA.

What compliance documentation does this breaker carry?

It is certified to EN/IEC 60947-2, with IP40 and IK07 protection ratings. Pollution degree 3 and overvoltage category III apply. The manufacturer provides standard compliance documentation (declaration of conformity) upon request.

MPN
C63H3TM630