Skip to main content
Schneider Electric C63H32D630

Schneider C63H32D630 Compact Breaker 70kA

MPNC63H32D630
Active

C63H32D630 - NSX630H 70KA AC 3P3D 630A 2.3 by SCHNEIDER ELECTRIC

$1,443.99Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

C63H32D630 key specifications
ParameterValue
Control typeToggle
Network typeAC
Protection typeL : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection
Product or component typeCircuit breaker
Long-time protection delay adjustment type trFixed
Short-time protection delay adjustment type tsdFixed
Short-time protection pick-up adjustment type isdAdjustable 9 settings
Instantaneous protection pick-up adjustment type iiFixed
Long-time pick-up adjustment type ir (thermal protection)Adjustable 9 settings
Voltage800 V AC 50/60 Hz
[Ue] rated operational voltage690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV

All specifications

C63H32D630 additional specifications
ParameterValue
Breaking capacity100 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2 70 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2 65 kA Icu 440 V AC 50/60 Hz IEC 60947-2 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2 35 kA Icu 525 V AC 50/60 Hz IEC 60947-2 20 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2 85 kA Icu 240 V AC 50/60 Hz UL 60947-4-1 65 kA Icu 480 V AC 50/60 Hz UL 60947-4-1 20 kA Icu 600 V AC 50/60 Hz UL 60947-4-1
Line rated current630 A 104 °F (40 °C)
Breaking capacity codeH 70 kA 415 V AC
[Ics] rated service breaking capacity100 kA 220/240 V AC 50/60 Hz IEC 60947-2 70 kA 380/415 V AC 50/60 Hz IEC 60947-2 65 kA 440 V AC 50/60 Hz IEC 60947-2 50 kA 500 V AC 50/60 Hz IEC 60947-2 11 kA 525 V AC 50/60 Hz IEC 60947-2 10 kA 660/690 V AC 50/60 Hz IEC 60947-2
Power dissipation per pole39.7 W
Network frequency50/60 Hz
Poles description3P
Protected poles description3D
Utilisation categoryCategory A
IK degree of protectionIK07 conforming to IEC 62262
IP degree of protectionIP40 conforming to IEC 60529
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Circuit breaker mounting modeFixed
Connection pitch1.8 in (45 mm)
Upside connectionFront
Downside connectionFront
Pollution degree3 IEC 60664-1
Relative humidity0...95 %
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000 m...5000 m with derating
Electrical shock protection classClass II front face
Depth4.3 in (110 mm)
Width5.5 in (140 mm)
Height10.04 in (255 mm)
Electrical durability8000 cycles 440 V In/2 4000 cycles 440 V In 6000 cycles 690 V In/2 2000 cycles 690 V In
Mechanical durability15000 cycles
StandardsEN/IEC 60947-2
RangeComPacT
CategoryUS10DE201101
Thermal memory20 minutes before and after tripping
Trip unit nameMicroLogic 2.3
Number of slots6
Local signallingFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
Trip unit rating630 A 104 °F (40 °C)
Device short nameNSX630H
Device applicationDistribution
Overvoltage categoryIII
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes EN/IEC 60947-2
Trip unit protection functionsLSoI
Zone selective interlocking ZSIWithout
Ambient air temperature for storage-58...185 °F (-50...85 °C)
Ambient air temperature for operation-13...158 °F (-25...70 °C)
[Tr] Long-Time delay adjustment range400 s 1.5 x Ir 16 s 6 x Ir 11 s 7.2 x Ir
[Ir] long-time protection pick-up adjustment range250...630 A
[Isd] short-time protection pick-up adjustment range1.5...10 x Ir
[Ii] instantaneous protection pick-up adjustment range6900 A
MPN