Skip to main content
Schneider Electric CV1BG2G0ZM511 — Contactors

Schneider Electric CV1BG2G0ZM511 TeSys B Contactor, 2P, 200

MPNCV1BG2G0ZM511
Active

Schneider Electric TeSys B series, CV1BG2G0ZM511 contactor, 2-pole, 200 A AC rated operational current, 690 V AC, AC-3/AC-1 utilisation categories, 220 V AC 50 Hz coil.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

CV1BG2G0ZM511 — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationMotor Resistive circuits, heating, lighting
CV1BG2G0ZM511 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)690 V AC
Utilisation categoryAC-3 AC-1
CV1BG2G0ZM511 — Contacts & Poles
ParameterValue
Pole configuration2P
CV1BG2G0ZM511 — Other specifications
ParameterValue
Device short nameCV1BG
Control circuit typeAC
Pole contact composition2 NO
Coil voltage220 V AC 50 Hz
Auxiliary contact composition1 NO + 1 NC
[Ie] rated operational current200 A AC for power circuit
Current rating code of contactorBG

Product details

It belongs to the TeSys range, Schneider's standard modular contactor family for motor starting and resistive load switching. Rated for utilisation categories AC-3 (squirrel-cage motor starting) and AC-1 (resistive loads, heating, lighting), this contactor handles the inrush and breaking demands of motor duty while also covering non-inductive switching.

The 200 A AC rated operational current under AC-1 means it can continuously carry and break resistive loads up to that level. Under AC-3 motor duty, the same 200 A frame supports direct-on-line starting of three-phase induction motors, where the make current can be 6–8× the rated current. The 2-pole configuration with 2 NO main poles suits single-phase motor switching, two-wire resistive loads, or phase-switching applications where a 3-pole contactor is unnecessary. The built-in auxiliary contact block (1 NO + 1 NC) provides feedback for the control circuit without requiring a separate add-on. Control voltage is 220 V AC at 50 Hz, so the coil is designed for direct connection to a standard European line-voltage control circuit. Verify your control transformer output matches this voltage before wiring.

This contactor class is installed in motor control centres, panel boards, and standalone enclosures for switching pumps, fans, compressors, conveyors, and heating banks. The TeSys B series is the standard-duty line within the TeSys family, positioned for general-purpose industrial applications where compact footprint and reliable AC coil operation are required.

Frequently asked questions

What are the key ratings of CV1BG2G0ZM511?

Rated operational current 200 A AC for the power circuit, rated operational voltage 690 V AC, utilisation categories AC-3 and AC-1, control circuit voltage 220 V AC 50 Hz, 2-pole with 2 NO main contacts and 1 NO + 1 NC auxiliary contacts.

What is the TeSys range and TeSys B product name?

The CV1BG2G0ZM511 belongs to the TeSys range and carries the product name TeSys B. TeSys is Schneider Electric's standard modular contactor and motor-protection family; TeSys B is the base series within that range.

What compliance documentation is available for this contactor?

As a Schneider Electric TeSys product, it is manufactured under IEC/EN 60947-4-1 standards. Compliance documentation including RoHS and REACH declarations is available from Schneider's documentation portal for the CV1BG order code.

MPN
CV1BG2G0ZM511