The G12F3A40 is a 3-pole GoPact MCCB 125 with a TM-D thermal-magnetic trip unit rated 40 A at 40 °C. The LI protection curve (thermal for overload, magnetic for short-circuit) is the standard for cable and busbar protection in distribution applications. Rated operational voltage is 415 V AC 50/60 Hz, with an insulation voltage of 440 V AC, both conforming to EN/IEC 60947-2. The utilisation category A means it is not intended for motor switching under load — it is a distribution breaker, not a motor starter protector.
Fixed mount on a backplate, with front-connect screw terminals on both line and load sides. The 25 mm connection pitch matches standard busbar systems. IP20 finger-safe protection on the front.