Skip to main content
Schneider Electric G12F4F40 — Miniature Circuit Breakers (MCB)

Schneider G12F4F40 GoPact MCCB 125, 40 A, 30 kA, 4P

MPNG12F4F40
Active

Schneider Electric GoPact MCCB 125, G12F4F40, 4P, 40 A at 40 °C, TM-D thermal-magnetic trip unit, breaking capacity 30 kA at 380/415 V AC, IP20, screw terminals, fixed mount.

$103.47Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12F4F40 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12F4F40 — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12F4F40 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12F4F40 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12F4F40 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12F4F40 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12F4F40 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity30 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12F4F40 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric G12F4F40 is a GoPact MCCB 125 molded-case circuit breaker rated at 40 A at 40 °C, with a 30 kA breaking capacity at 380/415 V AC — that F-class performance (per IEC 60947-2) means it handles moderate fault levels typical of distribution sub-panels without needing an upstream current-limiting fuse. The 4-pole construction (4D protected poles) with neutral on the left suits three-phase distribution where you want a switched neutral. The TM-D trip unit gives thermal-magnetic LI protection: thermal for overload, magnetic for short circuit, no electronic adjustment — set-and-forget for fixed-load panels.

The 8000-cycle electrical endurance at rated current means it's designed for infrequent switching — it's a distribution breaker, not a motor-starting contactor. The IP20 finger-safe terminals are fine inside a locked panel; no washdown rating here.

Fixed-mount only — no plug-in base. Backplate mounting, 100 mm wide × 130 mm high × 60 mm deep, with a 25 mm connection pitch between poles. Screw terminals front-connected top and bottom; no rear-connect option. The toggle control is manual, not motor-operated. The grey RAL 7035 housing is the standard Schneider panel colour.

Frequently asked questions

What is the breaking capacity of G12F4F40?

The breaking capacity is 30 kA at 380/415 V AC (F performance level per IEC 60947-2).

Where can I buy G12F4F40?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What standards does G12F4F40 comply with?

It complies with EN/IEC 60947-1, EN/IEC 60947-2, and EN/IEC 60947-2 Annex H. Isolation suitability is confirmed per IEC 60947-2.

MPN