Skip to main content
Schneider Electric G12F4F50 — Miniature Circuit Breakers (MCB)

Schneider Electric G12F4F50 GoPact MCCB 125, 50 A, 30 kA, 4P

MPNG12F4F50
Active

Schneider Electric GoPact MCCB 125, G12F4F50, 4-pole thermal-magnetic circuit breaker, 50 A at 40 °C, 30 kA breaking capacity at 415 V AC, TM-D trip unit, IP20, grey (RAL 7035).

$103.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

G12F4F50 — Identification
ParameterValue
Product nameGoPact MCCB 125
Product range (series)GoPact MCCB
Product/component typeCircuit breaker
Device applicationDistribution
G12F4F50 — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)415 V AC 50/60 Hz conforming to EN/IEC 60947-2
Rated insulation voltage (Ui)440 V AC conforming to EN/IEC 60947-2
Rated impulse withstand voltage (Uimp)6 kV conforming to EN/IEC 60947-2
Utilisation categoryCategory A
Overvoltage categoryIII
G12F4F50 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)8000 cycles at 415 V In
Mechanical durability (cycles)30000 cycles
G12F4F50 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
G12F4F50 — Environmental
ParameterValue
Operating ambient temperature-20...55 °C
Storage ambient temperature-35...85 °C
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
G12F4F50 — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-2 EN/IEC 60947-2 Annex H
G12F4F50 — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity30 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 50 kA Icu at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
[Ics] rated service short-circuit breaking capacity15 kA at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 25 kA at 220/230 V AC 50/60 Hz conforming to EN/IEC 60947-2
G12F4F50 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric G12F4F50 is a GoPact MCCB 125 moulded-case circuit breaker rated 50 A at 40 °C with a 30 kA breaking capacity at 415 V AC, 50/60 Hz. This is a Category A breaker (no intentional short-time delay), suited for distribution duty in panelboards and switchboards where you need straightforward, reliable overcurrent protection without coordination complexity.

For a 50 A feeder in a 415 V distribution panel, that gives solid headroom against typical utility fault levels — most industrial services sit well below 30 kA. The TM-D trip unit has fixed thermal and magnetic settings — no adjustment dials — so what you see on the label is what you get. That keeps the BOM simple but means selectivity with downstream breakers must be checked by the I²t curves, not by tweaking the trip.

The toggle handle gives clear visual indication of tripped vs. ON/OFF status.

The grey (RAL 7035) colour is standard across the GoPact MCCB range.

Frequently asked questions

How do I get current pricing and availability for G12F4F50?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

What is the breaking capacity of G12F4F50?

The G12F4F50 has a 30 kA breaking capacity at 415 V AC, 50/60 Hz.

What trip unit does G12F4F50 use?

It uses a fixed thermal-magnetic TM-D trip unit providing LI protection — thermal for overload, magnetic for short-circuit.

MPN
G12F4F50