Schneider Electric TeSys GS, fuse switch disconnector body, 3 poles, BS fuse type, 315 A, 400 V AC-23B, 80 kA SCCR.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

GS1PPBR3 — Identification
ParameterValue
Product / component typeFuse switch disconnector body
GS1PPBR3 — Contacts & Poles
ParameterValue
Pole configuration3P
GS1PPBR3 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529 (with terminal cover)
Protective treatment / pollution degreeTH
Fire resistance960 °C body conforming to IEC 60695-2-1 850 °C fuse cover conforming to IEC 60695-2-1
GS1PPBR3 — Approvals
ParameterValue
StandardsIEC 60269-1 IEC 60947-3 IEC 60269-2
GS1PPBR3 — Mechanical
ParameterValue
Width271 mm
Height205 mm
Depth149 mm

Product details

The GS1PPBR3 is the body of a TeSys GS fuse switch disconnector — a 3-pole, BS-type fuse carrier rated for 315 A at 400 V in AC-23B duty (switching motor loads including occasional overload). The short-circuit withstand is 80 kA, meaning the body holds together under a bolted fault upstream of the fuses — the fuses themselves clear the energy.

Mounts on a rail or plate; the operating handle is on the right side. Dimensions are 271 mm wide by 205 mm high by 149 mm deep — factor the depth into enclosure gland-plate clearance. Power connections are via bars or screw terminals accepting 185…240 mm² flexible cable. Control-circuit and power-circuit terminals both torque to 25 N·m. IP20 with the terminal cover fitted (finger-safe, not washdown).

The GS1PPBR3 is officially obsolete per the manufacturer. If the design can absorb a parametric substitute, a current-production TeSys GS body with matching pole count, fuse type, and 315 A rating should be evaluated; the manufacturer's documentation for the GS1P family is the starting point for cross-referencing.

Designed to IEC 60269-1 (fuse), IEC 60269-2 (fuse for industrial applications), and IEC 60947-3 (switch-disconnectors). The body and fuse cover pass glow-wire tests at 960 °C and 850 °C respectively per IEC 60695-2-1. Rated insulation voltage 800 V AC, impulse withstand 8 kV. Protective treatment TH (tropicalised) for humid environments.

Frequently asked questions

What replaces the GS1PPBR3?

No official successor order code is published. A current-production TeSys GS body with the same pole count (3P), BS fuse type, and 315 A rating is the logical starting point for a parametric cross-reference.

What are the key ratings for the GS1PPBR3?

Rated 315 A at 400 V AC-23A/B (motor switching), with a short-circuit withstand of 80 kA. Breaking capacity is 2520 A at 400 V AC-23B; making capacity is 3150 A at the same condition. Conventional free-air thermal current is 315 A at 40 °C.

What standards does the GS1PPBR3 comply with?

It complies with IEC 60269-1, IEC 60269-2, and IEC 60947-3. The enclosure is IP20 with terminal cover, and the body has tropicalised protective treatment (TH).

MPN