Specifications
| Parameter | Value |
|---|---|
| Dimension type | Made to measure |
| Range of product | Canalis KT |
| Product or component type | Straight length |
| Maximum voltage drop | <0.0022 V with power factor = 0.7 at 50 Hz with 1A for 100 m long |
| Voltage | 1000 V |
| [Ue] rated operational voltage | 1000 V |
| [Ipk] rated peak withstand current | 248 kA |
| [Icw] rated short-time withstand current | 113 kA |
| Short-Circuit level | Standard version |
| [Ie] rated operational current | 2500 A at 35 °C |
| Network frequency | 50/60 Hz |
| IK degree of protection | IK08 conforming to IEC 62262 |
All specifications
| Parameter | Value |
|---|---|
| IP degree of protection | IP55 conforming to IEC 60529 |
| Mounting support | Horizontal support Vertical support |
| Mounting position | Horizontal/vertical |
| Earth conductor | Standard earth |
| Conductor material | Aluminium |
| Number of conductors | 3 |
| Width | 140 mm |
| Color | White (RAL 9001) |
| Height | 244 mm |
| Standards | IEC 61439-6 IEC 61439-1 |
| THDI | 0...15 % 2500 A 15...33 % 2000 A 33...100 % 1600 A |
| Length | 1501...2000 mm |
| Neutral position | Right |
| Device short name | KTA |
| Busbar description | Transport length |
| Device application | High power distribution |
| Provided equipment | Jointing unit |
| Mass per unit length | 25 kg/m |
| Thermal stress limit | 12769000 kA².s |
| Radiated magnetic field | 1.6 µT |
| Busbar trunking polarity | 3L + PE |
| Number of tap-off outlets | 0 |
| Ambient air temperature for operation | 35 °C (100 % of In) 40 °C (97 % of In) 45 °C (93 % of In) 50 °C (90 % of In) 55 °C (86 % of In) |