Skip to main content
Schneider Electric KTA3200EB420

Schneider Electric KTA3200EB420

MPNKTA3200EB420
Active

KTA3200EB420 by SCHNEIDER ELECTRIC

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

KTA3200EB420 key specifications
ParameterValue
Dimension typeFixed
Range of productCanalis KT
Product or component typeStraight length
Maximum voltage drop<0.0017 V with power factor = 0.7 at 50 Hz with 1A for 100 m long
Voltage1000 V
[Ue] rated operational voltage1000 V
[Ipk] rated peak withstand current189 kA
[Icw] rated short-time withstand current86 kA
Short-circuit levelStandard version
[Ie] rated operational current3200 A at 35 °C
Network frequency50/60 Hz
IK degree of protectionIK08 conforming to IEC 62262

All specifications

KTA3200EB420 additional specifications
ParameterValue
IP degree of protectionIP55 conforming to IEC 60529
Mounting supportHorizontal support Vertical support
Mounting positionHorizontal/vertical
Earth conductorStandard earth
Conductor materialAluminium
Number of conductors4
Electrical connectionBolted connection
Width140 mm
ColorWhite (RAL 9001)
Height324 mm
StandardsIEC 61439-6 IEC 61439-1
THDI0...15 % 3200 A 15...33 % 2500 A 33...100 % 2000 A
Length2000 mm
Neutral positionRight
Device short nameKTA
Busbar descriptionDistribution length
Device applicationHigh power distribution
Provided equipmentJointing unit
Thermal stress limit7396000 kA².s
Radiated magnetic field2.1 µT
Busbar trunking polarity3L + N + PE
Number of tap-off outlets1
Tap-Off unit compatibilityBolt-on tap-off unit from Canalis KT
Ambient air temperature for operation35 °C (100 % of In) 40 °C (97 % of In) 45 °C (93 % of In) 50 °C (90 % of In) 55 °C (86 % of In)
MPN
KTA3200EB420