Schneider Electric LV947600WSP
MPNLV947600WSP
Active
MicroLogic Active 2.0EP control unit, wireless, MasterPacT MTZ1/MTZ2/MTZ3 circuit breakers, LI, spare part
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Display type | LCD display - 320 x 240 pixels |
| Network type | AC |
| Metering type | Current I1, I2, I3, Iavg RMS Neutral current IN RMS Ground fault current Ig RMS Voltage V12, V23, V31, VLLavg RMS Voltage V1N, V2N, V3N, VLNavg RMS Active power P, P1, P2, P3 total Active energy Ep IN/OUT/tot Power factor Demand current I1, I2, I3, In, Iavg Frequency Phase sequence Unbalance current |
| Protection type | Overload protection (long time) conforming to ANSI 49 Instantaneous short-circuit protection conforming to ANSI 50 |
| Type of measurement | Energy meter Ammeter |
| Product or component type | Control unit |
| Long time delay adjustment type | Adjustable in step of 0.5 s |
| Network and machine diagnosis type | System (HMI) health state overview: circuit breaker health state Contacts state: circuit breaker health state MicroLogic service life: circuit breaker health state Tripping cause indication: circuit breaker tripping cause Identification card: diagnostic data Configured alarms synthesis: diagnostic data Monitored function: diagnostic data Operation: diagnostic data MicroLogic test: test Protection test: test Selectivity test: test Trip context information: crisis management Operation: advanced diagnostic Breaker service life: circuit breaker health state |
| Instantaneous pick-up adjustment type ii | Adjustable |
| Measurement voltage | 208...828 V AC 50/60 Hz phase to phase 120...480 V AC 50/60 Hz phase to neutral |
| [Ue] rated operational voltage | 690 V AC, +/- 10 % |
| Network frequency | 50/60 Hz |
All specifications
| Parameter | Value |
|---|---|
| Frequency measurement range | 40...70 Hz |
| Poles | 4P 3P |
| Protected poles description | 3P 3d 4P 3d 4P 3d + N/2 4P 4d 4P 3d + OSN |
| Communication port protocol | Bluetooth 5.0 LE peer to peer 30 kbit/s NFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds |
| Mounting mode | Fixed Drawout |
| Mounting location | Indoor use only |
| Pollution degree | 3 conforming to IEC 60947-1 |
| Relative humidity | 95 % at 55 °C conforming to IEC 60068-2-30 |
| Operating altitude | <= 5000 m with operational voltage derating 560 V AC |
| Standards | EN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 60255-1 EN/IEC 61010-1 IEEE 802.15.4 |
| Range | MasterPacT |
| Accuracy | Class 0.5: unbalance voltage |
| Data recording | Data logs Event logs Alarm logs Time stamping Maintenance logs Min/max of instantaneous values |
| Thermal memory | Yes |
| Trip unit rating | 250 A 400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A |
| Device short name | MicroLogic Active 2.0 EP |
| Energy management | Measurement ,active, reactive and apparent energy Measurement ,electrical network Measurement ,energy |
| Device application | Equipment protection, monitoring and control |
| Measurement accuracy | Current I1, I2, I3, Iavg, Idemand for MTZ1: +/- 1.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 1.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 1.5 % 80...6300 x 1.2 A Neutral current IN: +/- 1.5 % Ground fault current Ig: +/- 10 % Voltage V12, V23, V31, VLLavg: +/- 0.5 % 208...690 x 1.2 V Voltage V1N, V2N, V3N, VLNavg: +/- 0.5 % 120...400 x 1.2 V Active power P, P1, P2, P3, Pdemand: +/- 2 % Active energy Ep IN/OUT/tot: +/- 2 % Power factor: +/- 2 % Frequency: +/- 0.005 Hz Unbalance current: +/- 0.5 % |
| Measurement category | Category IV conforming to IEC 61010-2-30 |
| Overvoltage category | IV conforming to IEC 61010-1 |
| Trip unit technology | Electronic |
| Neutral protection setting | 1 x Ir (4P 4d) 0.5 x Ir (4P 3d + N/2) 1.6 x Ir (4P 3d + OSN) No protection (4P 3d) |
| Circuit breaker application | Distribution IEC standard |
| Environmental characteristic | Wet location not approved for use conforming to IEC 61010-1 |
| Electromagnetic compatibility | Electrostatic discharge immunity test conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Conducted and radiated emissions A conforming to CISPR 22 |
| Trip unit protection functions | LI |
| Zone selective interlocking ZSI | Without |
| Ambient air temperature for operation | -25...70 °C (operating) -35 °C (for start-up of product) |
| [Tr] Long-Time delay adjustment range | 0.5...30 s at 6 x Ir |
| [Ir] long time pick-up adjustment range | 0.4...1 x In adjustable in step of 1 A |
| [Ii] instantaneous pick-up adjustment range | 1.5...10 x Ir adjustable in step of 0.1 x Ir |
| [Li mode] instantaneous delay adjustment range | 20 ms in standard |