MicroLogic Active 2.0EP control unit, wireless, MasterPacT MTZ1/MTZ2/MTZ3 circuit breakers, LI, spare part

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LV947600WSP key specifications
ParameterValue
Display typeLCD display - 320 x 240 pixels
Network typeAC
Metering typeCurrent I1, I2, I3, Iavg RMS Neutral current IN RMS Ground fault current Ig RMS Voltage V12, V23, V31, VLLavg RMS Voltage V1N, V2N, V3N, VLNavg RMS Active power P, P1, P2, P3 total Active energy Ep IN/OUT/tot Power factor Demand current I1, I2, I3, In, Iavg Frequency Phase sequence Unbalance current
Protection typeOverload protection (long time) conforming to ANSI 49 Instantaneous short-circuit protection conforming to ANSI 50
Type of measurementEnergy meter Ammeter
Product or component typeControl unit
Long time delay adjustment typeAdjustable in step of 0.5 s
Network and machine diagnosis typeSystem (HMI) health state overview: circuit breaker health state Contacts state: circuit breaker health state MicroLogic service life: circuit breaker health state Tripping cause indication: circuit breaker tripping cause Identification card: diagnostic data Configured alarms synthesis: diagnostic data Monitored function: diagnostic data Operation: diagnostic data MicroLogic test: test Protection test: test Selectivity test: test Trip context information: crisis management Operation: advanced diagnostic Breaker service life: circuit breaker health state
Instantaneous pick-up adjustment type iiAdjustable
Measurement voltage208...828 V AC 50/60 Hz phase to phase 120...480 V AC 50/60 Hz phase to neutral
[Ue] rated operational voltage690 V AC, +/- 10 %
Network frequency50/60 Hz

All specifications

LV947600WSP additional specifications
ParameterValue
Frequency measurement range40...70 Hz
Poles4P 3P
Protected poles description3P 3d 4P 3d 4P 3d + N/2 4P 4d 4P 3d + OSN
Communication port protocolBluetooth 5.0 LE peer to peer 30 kbit/s NFC peer to peer 28800 bauds conforming to ISO 15963 USB peer to peer 115 kbauds
Mounting modeFixed Drawout
Mounting locationIndoor use only
Pollution degree3 conforming to IEC 60947-1
Relative humidity95 % at 55 °C conforming to IEC 60068-2-30
Operating altitude<= 5000 m with operational voltage derating 560 V AC
StandardsEN/IEC 60947-2 EN/IEC 60092-202 EN/IEC 60947-1 EN/IEC 60255-1 EN/IEC 61010-1 IEEE 802.15.4
RangeMasterPacT
AccuracyClass 0.5: unbalance voltage
Data recordingData logs Event logs Alarm logs Time stamping Maintenance logs Min/max of instantaneous values
Thermal memoryYes
Trip unit rating250 A 400 A 630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A 6300 A
Device short nameMicroLogic Active 2.0 EP
Energy managementMeasurement ,active, reactive and apparent energy Measurement ,electrical network Measurement ,energy
Device applicationEquipment protection, monitoring and control
Measurement accuracyCurrent I1, I2, I3, Iavg, Idemand for MTZ1: +/- 1.5 % 40...1600 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ2: +/- 1.5 % 40...4000 x 1.2 A Current I1, I2, I3, Iavg, Idemand for MTZ3: +/- 1.5 % 80...6300 x 1.2 A Neutral current IN: +/- 1.5 % Ground fault current Ig: +/- 10 % Voltage V12, V23, V31, VLLavg: +/- 0.5 % 208...690 x 1.2 V Voltage V1N, V2N, V3N, VLNavg: +/- 0.5 % 120...400 x 1.2 V Active power P, P1, P2, P3, Pdemand: +/- 2 % Active energy Ep IN/OUT/tot: +/- 2 % Power factor: +/- 2 % Frequency: +/- 0.005 Hz Unbalance current: +/- 0.5 %
Measurement categoryCategory IV conforming to IEC 61010-2-30
Overvoltage categoryIV conforming to IEC 61010-1
Trip unit technologyElectronic
Neutral protection setting1 x Ir (4P 4d) 0.5 x Ir (4P 3d + N/2) 1.6 x Ir (4P 3d + OSN) No protection (4P 3d)
Circuit breaker applicationDistribution IEC standard
Environmental characteristicWet location not approved for use conforming to IEC 61010-1
Electromagnetic compatibilityElectrostatic discharge immunity test conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 1.2/50 µs shock waves immunity test conforming to IEC 61000-4-5 Conducted RF disturbances conforming to IEC 61000-4-6 Conducted and radiated emissions A conforming to CISPR 22
Trip unit protection functionsLI
Zone selective interlocking ZSIWithout
Ambient air temperature for operation-25...70 °C (operating) -35 °C (for start-up of product)
[Tr] Long-Time delay adjustment range0.5...30 s at 6 x Ir
[Ir] long time pick-up adjustment range0.4...1 x In adjustable in step of 1 A
[Ii] instantaneous pick-up adjustment range1.5...10 x Ir adjustable in step of 0.1 x Ir
[Li mode] instantaneous delay adjustment range20 ms in standard