Skip to main content
Schneider Electric NTSDDO0212HK

Schneider Electric NTSDDO0212HK

MPNNTSDDO0212HK
Active

Discrete Output Module + Base, 2 Isolated Out, 24V DC, 2A, Source, Protected, 1/2/3 Wires, Hardened, Modicon Edge I/O NTS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

NTSDDO0212HK key specifications
ParameterValue
Range of productModicon Edge I/O NTS
Power supply typeBus power from power supply bus (24 Vdc) Field power from power supply field (24 Vdc) Optional field power from external power supply (24 Vdc)
Output protection typeTransient voltage suppression per channel Short circuit protection per channel Overload/thermal protection per channel Reverse polarity protection for internal supply per module
Product or component typeDiscrete output module kit
Maximum voltage drop<0.35 V per channel (from internal power distribution module) DC
Discrete output voltage24 V DC
Rated operational voltage limits20.4...28.8 V DC
Discrete output current2 A per channel 4 A per module
Maximum leakage current0.0001 mA per channel
Typical current consumption27.6 mA 24 V DC on the Bus current 0 mA 24 V DC on the internal field current minimum 4000 mA 24 V DC on the internal field current maximum
Power dissipation in1.22 W maximum at 24 V DC
Discrete output frequency1 kHz for resistive load 0.5/LI² Hz for inductive load

All specifications

NTSDDO0212HK additional specifications
ParameterValue
IP degree of protectionIP20
Mounting supportTop hat type TH35-7.5 IEC 60715 Top hat type TH35-15 IEC 60715
Response time on output70 µs turn-on 120 µs turn-off
Pollution degree2
Shock resistance15 g 11 ms with and without accessory)
Relative humidity5...95 % without condensation
Operating altitude0...6561.68 ft (0...2000 m) without derating 2000...5000 m with derating
Vibration resistance1 g without accessory 2 g with accessory
Depth3.1 in (80 mm)
Width0.6 in (15 mm)
Height3.9 in (100 mm)
Housing colourGrey
StandardsEN/IEC 61131-2 EN 61010-2-201 UL 61010-2-201 IACS E10 EN/IEC 61000-6-5, interface type 1 and type 2 EN/IEC 61850-3, location G EN/IEC 60079-0 EN 50155 EN 50121-4 EN 50121-5
MarkingCE UKCA CULus RCM
CategoryUS1PC3318214
Directives2014/30/EU - electromagnetic compatibility 2014/34/EU - ATEX directive 2014/35/EU
Operating modeSynchronous/Isochronous
Kit compositionNTSDDO0212H module NTSXBA0100H base
Local signalling1 LED (green) for module operating (RUN) 1 LED per channel (green) for channel diagnostic 1 LED (red) for module error (ERR)
Output diagnosticPower supply error per channel External power supply error per channel Short circuit error per channel
Device applicationIndustrial application in severe environment
Output wiring mode1, 2 or 3 wires
Mandatory accessoryNTSXTB12_1_H terminal block
Protective treatmentConformal coating
Discrete output logicPositive logic (source)
Hot swapping fallbackYes
Maximum tungsten load<48 W
Discrete output number2 transistor
Paralleling of outputsYes for redundancy Yes for double current Yes for same group (maxium 2)
Group of output channels2 groups of 1 channels
Isolation between channels500 V AC
Environmental characteristicGas resistant CX & GX combined Salt spray resistant
Isolation between channels and bus1500 V AC
Ambient air temperature for storage-40...185 °F (-40...85 °C)
Ambient air temperature for operation-40...158 °F (-40...70 °C)
Isolation between channels and ground1500 V AC
MPN
NTSDDO0212HK