Skip to main content
Schneider Electric REL52900

Schneider Electric REL52900

MPNREL52900
Active

Square D REL52900 Arc Flash Prot Unit|Square D REL52900 Arc Flash Prot Unit

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

REL52900 key specifications
ParameterValue
Protection typeArc suppression 50ARC
Range of productEasergy ARC
Type of measurementArc
Product or component typeArc fault detection device
Binary input voltage24...240 V AC/DC 250 V)
Output current limits20 mA 24 V DC
Power supply24...240 V AC/DC
I/O channels3 binary 1 binary current input 4 arc sensor 1 digital
IP degree of protectionIP20 conforming to IEC 60529
MountingFlush DIN rail
Mounting supportPanel
Connections - terminalsRemovable screw terminal block

All specifications

REL52900 additional specifications
ParameterValue
Relative humidity0...95 % without condensation
Operating altitude<= 6561.68 ft (2000 m)
DepthTotal : 5.0 in (126 mm)
WidthTotal: 2.8 in (70 mm)
HeightTotal: 5.3 in (135 mm)
StandardsEN/IEC 60255-1 EN 60255-27
HMILED 11
RangePowerLogic
CategoryUS1PL1S11405
Control functionsSwitchgear internal arc detection
Device short nameA125
Relay applicationArc flash
Protective treatmentConformal coating
Mechanical robustnessVibrations class 2) IEC 60255-21-1 Shocks class 2) IEC 60255-21-2 Earthquakes criteria A) level 2 IEC 60255-21-3 Vibrations Fc) IEC 60068-2-6 Shocks Ea) IEC 60068-2-27
Environmental characteristicExposure to dry heat Bd EN/IEC 60068-2-2 Exposure to cold Ad EN/IEC 60068-2-1 Exposure to damp heat in service Db EN/IEC 60068-2-30 Exposure to damp heat in service Cab EN/IEC 60068-2-78 Temperature variation Nb IEC 60068-2-14
Electromagnetic compatibilityEmission tests IEC/EN 60255-26 ed. 3 Emission tests class A EN 55022 Emission tests CISPR 22 Emission tests class A EN 55011 Emission tests IEC 60255-25 Emission tests CISPR 11 EMC immunity A IEC/EN 60255-26 ed. 3 Damped oscillatory wave EN/IEC 61000-4-18 Electrostatic discharge level 4 EN/IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 EN/IEC 61000-4-3 Electrical fast transient level 4 EN/IEC 61000-4-4 Surge immunity test level 3 EN/IEC 61000-4-5 Immunity to conducted interference caused by radio-electrical fields level 3 EN/IEC 61000-4-6 Immunity to magnetic fields EN/IEC 61000-4-8 Immunity to magnetic fields level 5 EN/IEC 61000-4-9 Immunity to voltage dips power lines (DC) EN/IEC 61000-4-29 Immunity to voltage dips EN/IEC 61000-4-11 Immunity to ripple EN/IEC 61000-4-17
Ambient air temperature for storage-40...176 °F (-40...80 °C)
Ambient air temperature for operation-40...149 °F (-40...65 °C)
MPN